Before an Insulation Test

The Tester includes features and functions that let you adapt the test to your
requirements. These features let you:
define a test voltage
make a ramp test selection
set a time limit (duration) for the test
measure polarization index (PI)
measure dielectric absorption ratio (DAR)
measure capacitance
Use these alone or in combination. Set, clear, or account for (as appropriate)
each feature before you start an insulation test. The features are discussed in
this section.

Preset Test Voltage Selection

To make a preset test voltage selection:
1. With the Tester turned on, push  to select TEST VOLTAGE.
2. Push  or  to scroll through the preset test voltage options (250 V,
500 V, 1000 V, 2500 V, 5000 V, and 10,000 V).
The test voltage selection shows in the upper-right of the display.
16