Connection Setting; Serial Setting - Toshiba T-PSV Operation Manual

Programmable controller prosec t-series dde server
Table of Contents

Advertisement

4.2.1 Connection setting

The connection setting specifies the connection name, type of connection (Ethernet or Serial),
Time-out setting, and Update cycles (High, Middle and Low).
The setting details and the column order are as follows.
Setting ID
Connection name
Type of connection
Time-out (in second)
High update cycle
(in second)
Middle update cycle
(in second)
Low update cycle
(in second)

4.2.2 Serial setting

If the connection setting is serial, the serial setting is required.
The serial setting specifies the computer's communication port, baudrate, data bit length, parity,
and stop bit length.
The setting details and the column order are as follows.
Setting ID
Communication port
Baudrate
Data bit length
Parity
Stop bit length
Note) When the programmer port or TOSLINE-S20 is used, set the communication parameter
as follows.
• Baudrate : 9600 bps
• Data bit :
• Parity :
• Stop bit :
C
Any name (within 11 characters)
Ethernet or Serial
Response time-out setting
Minimum 0.2 (0.1 s increments)
High-speed update cycle setting
Minimum 0.2 (0.1 s increments)
Middle-speed update cycle setting
Minimum 0.3 (0.1 s increments)
It must be larger than high-speed setting
Low-speed update cycle setting
Minimum 0.4 (0.1 s increments)
It must be larger than middle-speed setting
CS
COM1, COM2, COM3, or COM4
1200, 2400, 4800, 9600, or 19200 bps
8 (fixed)
ODD, EVEN, or NON
(upper and lower cases are not distinguished)
1 or 2
8 bits
Odd (for Programmer port) or Even (for TOSLINE-S20) at default state
(Parity can be changed by user)
1 bit
4. Configuration File
Operation Manual
19