Honeywell Micronik 200 Specification Data page 3

Temperature controller with real-time clock
Table of Contents

Advertisement

CONTROL AND CONFIGURATION PARAMETER
The controller includes two groups of settings (A and B) for control and configuration parameters that are automatically
selected during programming. For parameter Ctrltyp = Lo setting A is selected and for parameter Ctrltyp = Hi setting B is
selected.
Control Parameter
No.
Name
P.01
W1
Main setpoint for input T1
P.02
Wlim
Limit setpoint (low or high) for input T2
P.03
Wcomp
Compensation changeover point for input T3
P.04
Wi
Winter compensation authority
P.05
Su
Summer compensation authority
P.06
Wcas
Submaster or cascade setpoint
P.07
Rcas
Cascade reset span adjustment
P.08
Xp1
Throttling range (main control loop) T1
Throttling range (cascade or limit control loop)
P.09
Xp2
T2
1)
P.12
tr1
Reset time (main control loop) T1
1)
P.13
tr2
Reset time (cascade or limit control loop) T2
P.15
Ystart
Start point for mid range shift of output Y1
P.16
SOFFS
Offset of main setpoint in Standby mode
P.17
T1Cal
Calibration of temperature sensor T1
P.18
T2Cal
Calibration of temperature sensor T2
P.19
T3Cal
Calibration of temperature sensor T3
P.21
RuntimeY1 Actuator run time for Y1
P.24
NightLow
Night low limit against temperature extremes
P.25
NightHigh
Night high limit against temperature extremes
P.26
NOFFS
Offset of main setpoint in Night mode
Config. Parameter
No.
Name
2)
C.04
Ctrltyp
Lo = 0...50°C, Hi1 = 0...130°C, Hi2 = 0...130°C
0 = internal (default), 1 = 5 K (953...1053 τ), 2 = 5 K (100 kτ...0 τ),
C.05
CPATYP
3 = 15 ... 30C (10...20 kτ), 4 = 5 K (0...10 kτ),
5 = 15 ... 30C (0...100 kτ), 6 = 0...50C or 0...130C (0...100 kτ)
0= floating, 1= 2 stage ON/OFF, 2= 3 stage ON/OFF, 3 = pwm, 4 = unconfig.
C.08
Y1Mode
(safe state is configured prior to controller's start-up)
C.12
T2ext
0 = T2 installed
C.13
LimTyp
0 = Low limit
C.14
Senstyp
0 = Auto detection
Output Y1 used for:
C.15
Y1CTRF
C.16
AddHour
Adjusts the month for winter/summer time change: 0 (disabled) = Min. 12 = Max.
C.17
SubHour
Adjusts the month for summer/winter time change: 0 (disabled) = Min. 12 = Max.
3)
C.18
PSTG_H
Prestart gradient for heating:
3)
C.19
PSTG_C
Prestart gradient for cooling:
C.21
Adapt
Optimum Start Self Adaption speed:
2)
C.22
Adr
Serial communication address:
C.23
0 = No default programming
DefProg
1)
for tr > 2 min
resolution = 0.5 min , for tr < 2 min
2)
actual value will not be changed during reset to default parameter
3)
can be overwritten by controller for self-adaption purposes, resolution = 0.01 K/min
Parameter Description
Values
1 = Initiates default programming
resolution = 10 sec
R7426A TEMPERATURE CONTROLLER
Setting A / Setting B
Low
0
50/130
5 / 30
50/130
-5
-350
-100
OFF, 0
50/130 20/OFF
0
0.5
0.5
OFF, 20 s
OFF, 20 s
-20
0
-20
-20
-20
6
OFF, 8
19 / 80
OFF, 21
0
1 = T1 signal used for T2
1 = High limit
1 = NTC sensor type
0 = cooling, 1 = heating
2 = summer/winter changeover
0 (disabled) = Min.
2 = Max.
0 (disabled) = Min.
0 = Min.
100 = Max.
0 = Min.
255 = Max.
3
Reso-
lution
High
Default
21 / 70
0.5
16 / 90
1
40
20
1
+350
0
2
+100
0
1
0.5
40
10
0.5
40
2
0.5
40
10
0.5
20min
OFF
10/0.5
20min
OFF
10/0.5
+20
0
0.5
10
2
0.1
+20
0
0.1
+20
0
0.1
+20
0
0.1
180
60
1
OFF
1
40
OFF
1
30
5 / 20
0.1
Default
A / B
Lo
0
4
0
0 / 1
0
0 / 1
3
10
0
2 = Max.
0
50
254
0
EN0B-0299GE51 R0104
Unit
C
C
C
%
%
C
K
K
K
sec/min
sec/min
K
K
K
K
K
sec
C
C
K
Unit
month
month
K/min
K/min
%