3-3. PIPE CONNECTION
• Fasten flare nut with a torque wrench as specified in the table (refer to 3-23.
• When fastened too tight, flare nut may eventually break and cause refrigerant
leakage.
Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
• Apply a thin coat of refrigerant oil (J) on the seat surface of pipe.
• To connect, first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table above as a guideline for indoor unit side joints,
and tighten
using two wrenches.
Excessive tightening
damages the flare section.
Outdoor
unit connection
Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure
detailed in Indoor unit connection.
• For tightening,
use a torque wrench or spanner.
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection on the outdoor unit.
• When piping has to be installed through a ceiling, closet or where the temperature
and humidity are high, use additional field-supplied
insulation to prevent condensa-
tion.
4-1. PURGING PROCEDURES AND LEAK TEST
1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe.
2) Connect gauge manifold
valve and vacuum pump to service port of stop valve on the
gas pipe side of the outdoor unit.
0.101 MPa
Compound
pressure
gauge
"4 to 5 turns
Stop valve cap
(-30 in.Hg
(for R410A)
(Torque
19.6 to
Pressure
gauge
_Ctose
29.4 N,m. 200
Stop valve
(for R410A)
*open_-_
m
to300kgf,
cm)
forLIQUID
Gaug .....
ifeld valve
_:""
,._%
(for R410A)
"_ _.-.__._
Handle
Low
Handle High
Hexagonal wrench
Charge hose
Stop valve for
(for R410A)
Service
port cap
(Torque
13.7 to
17.7 N°m,
Adapter
for pre-
180 kgfocm)
venting the back
flow
Vacuum pump (or the vacuum
pump with the function
to
prevent the back flow)
IPrecautions
when usin,q the control valve I When attachina the control valve
to the service Port valve core may
deform or loosen if excess pressure
is aDDlied. This may cause ads leak.
Close
Charge
hose
Body
When attaching the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten partA. Do not tighten
part Aor turn the body when valve
core is in open position.
3) Run the vacuum pump 15 minutes or more.
4) Check the vacuum with the gauge manifold valve, then close it and shut off the vacuum
pump.
5) Leave as it is for one or two minutes.
Make sure pointer gauge manifold valve remains
in the same position. Confirm
that pressure
gauge
shows -0.101
MPa [Gauge] (-30
in.Hg [-760 mmHg]).
6) Quickly remove gauge manifold valve from service port of stop valve.
7) After refrigerant
pipes are connected
and evacuated,
fully open all stop valves on both
sides of gas pipe and liquid pipe. Operating
the unit without fully opening
the valves
lowers the performance
and causes problems.
8) Refer to 1-3. SPECIFICATIONS,
and charge
the prescribed
amount
of refrigerant
if
needed. Be sure to charge slowly with liquid refrigerant.
Otherwise,
composition
of the
refrigerant in the system may be changed and affect performance
of the air conditioner.
9) Tighten cap of service port.
10) Conduct a leak test
4-2. TEST RUN
1) Insert power supply plug into the power outlet and/or turn
on the breaker.
2) Press the E.O. SW once. Test run will be performed
for
30 minutes.
If the power lamp blinks every 0.5 seconds,
inspect the indoortoutdoor
unit connecting
wire (A). After
the test run, emergency
COOL mode (75°F [24°C] COOL)
will start.
3) To stop operation,
press the E.O. SW several times until
all LED lamps turn off. Refer to operating instructions
for
ienCYwitch
details.
(EO. SW)
Checking the remote (infrared)
signal reception
Press the ON/OFF button on the remote controller and listen for an audible indicator from
the indoor unit. Press the ONtOFF button again to turn the air conditioner
off.
Once the compressor
stops, the restart preventive
device operates
so the compressor
will not operate for 3 minutes to protect the air conditioner.
4-3. AUTO RESTART FUNCTION
This product is equipped with an auto restart function. When the power supply is cut off
during operation,
such as during blackouts, the function automatically
starts operation in
the previous setting once the power supply is resumed. (Refer to the operating instructions
for details.)
Caution:
• After test run or remote signal reception
check, turn off the unit with the E.O. SW or
the remote controller before turning off the power supply. If this procedure
is not per-
formed, the unit will automatically
begin operation when power supply is resumed.
To the user
• After installing the unit, explain to the user about auto restart function.
If auto restart function is unnecessary,
it can be deactivated.
Consult the service rep-
resentative
to deactivate the function.
Refer to the service manual for details.
4-4. REMOTE CONTROLLER SETTING
Set the slide switch of the remote controller according to where the indoor unit is installed
in the area. If the switch is not set correctly, the air conditioner
may not function properly.
Location of unit in area:
Left: Distance to objects (wall, cabinet, etc.) is less
(Left)(Center)(Right)
than 19-11/16 in. (50 cm) to the left
Center: Distance to objects (wall, cabinet, etc.) is
more than 19-11/16 in. (50 cm) to the left and right
Right: Distance to objects (wall, cabinet, etc.) is less
than 19-11/16 in. (50 cm) to the right
1) Remove the front lid.
2) Set the slide switch according to the installed position of the indoor unit.
3) Insert two (AAA) batteries.
4) Reattach the front lid.
SLIDE SWITCH
5) Press the RESET button gently using a thin instrument.
RESET 5 I_i
Installation
posi-
Left
Center
Right
button
tion
_'
_ _0"'_.
%
Slide switch
.__/_
Remote controller
display
I-_
_
_-I
4-5. EXPLANATION TO THE USER
Using the OPERATING
INSTRUCTIONS,
explain to the user how to use the air condition-
er (the remote controller, removing the air filters, placing or removing the remote controller
from the remote controller holder, cleaning methods, precautions for operation, etc.)
Recommend that the user read the OPERATING
INSTRUCTIONS
carefully.