Trane SEHJ090-162 Installation, Operation And Maintenance Manual page 179

Commercial single-zone rooftop air conditioners with cv, vav, szvav, or rr controls
Table of Contents

Advertisement

Table 57. Grease Recommendation
Recommended Grease
for Fan Bearings
Exxon Unirex #2
Mobil 532
Mobil SHC #220
Texaco Premium RB
Table 58. Air-Cooled Condenser—Refrigerant Coil Fin Data
Coil Fin
Tons
Coil Type
Config.
90
Evaporator
Enhanced
Hi-Cap Evap
Enhanced
Condenser
Enhanced
Internally
Evaporator
105
Internally
Hi-Cap Evap
Condenser
Enhanced
Internally
Evaporator
120
Internally
Hi-Cap Evap
Condenser
Enhanced
Internally
Evaporator
130
Internally
Hi-Cap Evap
Condenser
Enhanced
Internally
Evaporator
150
Condenser
Smooth
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer's
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
RT-SVX24J-EN
Recommended
Operating Range
-20 F to 250 F
Tube Dia.
Coil Rows Fins per foot
1/2
1/2
25 mm
1/2
Finned
1/2
Finned
25 mm
1/2
Finned
1/2
Finned
18 mm
1/2
Finned
1/2
Finned
18 mm
1/2
Finned
18 mm
Coil Face
Area (sq. ft.)
3
168
73.75
5
168
73.75
1
240
134
4
168
73.75
6
168
73.75
1
240
161
3
168
106.25
6
168
106.25
2
276
161
4
168
106.25
6
168
106.25
2
276
161
6
168
106.25
2
276
161
Fan Belt Adjustment
The supply fan belts and optional exhaust fan belts must
be inspected periodically to assure proper unit operation.
Replacement is necessary if the belts appear frayed or
worn. Units with dual belts require a matched set of belts
to ensure equal belt length.
When removing or installing the new belts, do not stretch
them over the sheaves. Loosen the belts using the belt
tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning or
Gates tension gauge (or equivalent), see
adjust the belt tension as follows:
1. To determine the appropriate belt deflection:
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64; the
resulting value represents the amount of belt
deflection that corresponds to the proper belt
tension.
Service and Maintenance
Tube Type
Internally Finned
Internally Finned
Microchannel
Internally Finned
Internally Finned
Microchannel
Internally Finned
Internally Finned
Microchannel
Internally Finned
Internally Finned
Microchannel
Internally Finned
Microchannel
Figure
121,
179