Method 2; Resetting Cooling And Heating Lockouts - Trane WSC036E Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners precedent — heat pump 3 – 10tons – 60 hz
Table of Contents

Advertisement

Troubleshooting
LED 4 (Service)
"On" indicates a clogged filter.
"Off" during normal operation.
"Flashing" indicates an evaporator or condensate
overflow switch failure.
Below is the complete listing of failure indication causes.
System Failure
Check the voltage between terminals 6 and 9 on J6, it
should read approximately 32 VDC. If no voltage is
present, a system failure has occurred. Refer to
the previous section for the recommended
troubleshooting procedure.
Cooling Failure
Cooling and heating set point (slide pot) on the zone
sensor has failed. Refer to the "Zone SensorTest
Procedure" section.
Zone temperature thermistor ZTEMP on ZTS failed.
Refer to the "Zone SensorTest Procedure" section.
CC1 or CC2 24 VAC control circuit has opened, check
CC1 & CC2 coils, and any of the controls below that
apply to the unit (HPC1, HPC2).
LPC1 has opened during the 3 minute minimum "on
time" during 4 consecutive compressor starts, check
LPC1 or LPC2 by testing voltage between the J1-8 & J3-
2 terminals on the RTRM and ground. If 24 VAC is
present, the LPC's has not tripped. If no voltage is
present, LPC's has tripped.
Service Failure
If the supply fan proving switch has closed, the unit will
not operate (when connected to RTOM), check the fan
motor, belts, and proving switch.
Clogged filter switch has closed, check the filters.
If the condensate overflow switch is closed, the unit
will not operate, check the float position is not in a
tripped condition and verify an "open" between wires
connecting to RTOM J6-1, J6-2.
Simultaneous Heat and Cool Failure
Emergency Stop is activated.

Method 2

The second method for determining system status is done
by checking voltage readings at the RTRM (J6).The system
indication descriptions and the approximate voltages are
listed below.
System Failure
Measure the voltage between terminals J6-9 & J6-6.
Normal Operation = approximately 32 VDC
System Failure = less than 1 VDC, approximately 0.75 VDC
48
Test Mode = voltage alternates between 32 VDC & 0.75
VDC
Heat Failure
Measure the voltage between terminals J6-7 & J6-6.
Heat Operating = approximately 32 VDC
Heat Off = less than 1 VDC, approximately 0.75 VDC
Heating Failure = voltage alternates between 32 VDC &
0.75 VDC
Cool Failure
Step 4
in
Measure the voltage between terminals J6-8 & J6-6.
Cool Operating = approximately 32 VDC
Cool Off = less than 1 VDC, approximately 0.75 VDC
Cooling Failure = voltage alternates between 32 VDC &
0.75 VDC
Service Failure
Measure the voltage between terminals J6-10 & J6-6.
Clogged Filter = Approximately 32 VDC.
Normal = Less than 1 VDC, approximately 0.75 VDC Fan
Failure = voltage alternates between 32 VDC & 0.75 VDC.
To use LED's for quick status information at the unit,
purchase a BAYSENS110* ZSM and connect wires with
alligator clamps to terminals 6 through 10. Connected each
respective terminal wire (6 through 10) from the Zone
Sensor to the unit J6 terminals 6 through 10.
Note: If the system is equipped with a programmable
zone sensor, BAYSENS119* the LED indicators will
not function while the BAYSENS110* is connected.

Resetting Cooling and Heating Lockouts

Cooling Failures and Heating Lockouts are reset in an
identical manner. Method 1 explains resetting the system
from the space; Method 2 explains resetting the system at
the unit.
Note: Before resetting Cooling Failures and Heating
Lockouts check the Failure Status Diagnostics by
the methods previously explained. Diagnostics will
be lost when the power to the unit is disconnected.
Method 1
To reset the system from the space, turn the "Mode"
selection switch at the zone sensor to the "Off" position.
After approximately 30 seconds, turn the "Mode"
selection switch to the desired mode, i.e. Heat, Cool or
Auto.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch "Off" and then "On" .
RT-SVX23F-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wsc120e

Table of Contents