Test Modes - Trane TSC060ED Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners precedent - electric/electric 5 – 10 tons – 50 hz
Table of Contents

Advertisement

Pre-Start
Table 6.
Service test guide for component operation
Test Step
Mode
Fan
Fan
On
1
Minimum
On
Ventilation
Economizer
2
On
Test Open
Cool
3
On
Stage 1
4
Cool
On
(Note 3)
Stage 2
5
Heat
On
(Note 3)
Stage 1
6
Heat
On
(Note 3)
Stage 2
Notes:
1. The condenser fans will operate any time a compressor is On,
providing the outdoor air temperatures are within the operating
values.
2. The exhaust fan will turn on anytime the economizer damper position
is equal to or greater than the exhaust fan setpoint.
3. Steps for optional accessories and non-applicable modes in unit will be
skipped.

Test Modes

There are three methods in which the "Test" mode can be
cycled at LTB-Test 1 and LTB-Test 2.
1. Step Test Mode - This method initiates the different
components of the unit, one at a time, by temporarily
shorting across the two test terminals for two to three
seconds.
For the initial start-up of the unit, this method allows
the technician to cycle a component "On" and have up
to one hour to complete the check.
2. Resistance Test Mode - This method can be used for
start-up providing a decade box for variable resistance
outputs is available. This method initiates the different
components of the unit, one at a time, when a specific
resistance value is placed across the two test
terminals. The unit will remain in the specific test mode
for approximately one hour even though the
resistance is left on the test terminals.
3. Auto Test Mode - This method is not recommended for
start-up due to the short timing between individual
component steps. This method initiates the different
components of the unit, one at a time, when a jumper
is installed across the test terminals. The unit will start
the first test step and change to the next step every 30
seconds.
At the end of the test mode, control of the unit will
automatically revert to the applied "System" control
method.
30
Econ 
(Note 2)
Comp1
Comp 2
Minimum
Position
Off
Off
Setpoint 0%
Selectable
Off
Off
Open
Off
Off
Minimum
(Note 1)
Off
Position
On
Minimum
(Note 1)
(Note 1)
Position
On
On
Minimum
Off
Off
Minimum
Off
Off
Heat 1
Heat 2
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
On
For unit test steps, test modes, and step resistance values
to cycle the various components, refer to
Upon power initialization, the Gas Ignition Module (IGN)
performs self-diagnostic checks to insure that all internal
controls are functional. It also checks the configuration
parameters against the components connected to the
system. The System LED located on the IGN module is
turned "On" within one second of power-up if internal
operation is okay.
Ohms
2.2K
3.3K
4.7K
6.8K
10K
15K
Table
6.
RT-SVX37B-EN