Section 2 Installation and Operation
Activating 4200 Serial
Output
Activating Sampler Serial
Output
Configuring the 2105 for
4200/6700
2-32
To activate the serial output function:
1. Go into the 4200 Set Up screen.
2. Use the arrow key to arrow to Optional Outputs.
3. Select the Serial Output option.
4. Under Periodic Serial Output, Choose ON.
5. Under the baud rate, Choose 2400 or 9600 (must match the
baud rate selected in the 2105).
6. Under Serial output interval- Choose between 15 seconds
to 15 minutes.
You can turn on the serial output before or after configuration of
the 4200.
The 6700 Series sampler must be in extended mode for serial
data output. To place the sampler in extended mode, at the main
menu press keys 6712.2.
To activate serial data output:
1. From the Other Functions menu, select Software Options.
2. On the Software Options screen, scroll and select Serial
Output. Select YES.
3. Under Port Settings, choose 2400 or 9600 (must match the
baud rate selected for the 2105).
4. Select the desired output interval between 15 seconds and 15
minutes.
To configure the 2105 for interfacing with the 4200/6700:
1. Connect the 2105 to the instrument's interrogator port.
(Contact the factory to order the appropriate cable.)
2. Connect to the 2105 with Flowlink and select the Modbus
tab.
3. In the Protocol Setup box:
a. The Protocol Type field is not used.
b. Baud: 2400 or 9600
c. Bits: 8
d. Parity: None
e. Stop Bits: 1
4. Click New Device and enter a Device Name for your instru-
ment. For the Address, enter 245. Click Continue.
5. In the Device Parameters window, use the register
addresses from Table 2-3 to enter all desired parameters,
taking care to specify "4 byte float" for Data Format. Also
refer to Table 2-3 for the correct Flowlink Data Type and
Units of Measure.
The Parameter Name can be anything you choose, provided
it is used only once.