MODEL:
PARLOR/PATRIOT
PREVENT HOUSE FIRES - Install and use only in accordance with the manufacturer's installation and operating instructions. Contact
your local building or fire officials about restrictions and installation inspection in your area. Refer to local building codes and
manufacturer's instructions for precautions required for passing a chimney through a combustible wall or ceiling. Do not run a
chimney connector through a combustible wall or ceiling. Do not connect this unit to a chimney flue serving another appliance.
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local
building or fire officials. For use with solid wood fuel only (cord wood). Operate with feed door closed - open to feed fire only. Do not
use a grate to elevate fire - build fire directly on hearth. DANGER: Risk of electrical shock. Disconnect power supply before servic-
ing. Route power cord away from unit. Do not route power cord over or under appliance.
STANDARD RESIDENTIAL FREESTANDING INSTALLATIONS REQUIRE: 6" diameter, minimum 24 MSG black or 25 MSG blued steel
connector, with listed (type HT) factory-built chimney, suitable for use with solid fuels or masonry chimney. Do not install in a
sleeping room of a mobile home.
ALCOVE INSTALLATIONS REQUIRE: One of the Listed doublewall connectors listed below. Maximum alcove depth 48", minimum
alcove height 84", minimum alcove width 59-5/8" (Patriot) 60" (Parlor).
MOBILE HOME INSTALLATIONS REQUIRE: One of the Listed doublewall connectors listed below. Mobile home installations also
require outside air - use the Lopi optional outside air boot.
• DURAVENT model DVL with DURA-PLUS chimney
• AMERI-TEC model DCC with model HS chimney
• SECURITY model DP with SECURITY model ASHT or S2100 chimney
CLEARANCE
REQUIREMENTS:
A.
SIDEWALL TO UNIT
B.
BACKWALL TO UNIT
C.
CORNERWALL TO UNIT
D.
SIDEWALL TO CONNECTOR
E.
BACKWALL TO CONNECTOR
F.
CORNERWALL TO CONNECTOR
MINIMUM CLEARANCES TO COMBUSTIBLES:
BACKWALL
ADJACENT WALL
E
B
D
45˚
STOVE
A
Certified to comply with July 1990 particulate emission standards.
2004
2005
2006
IGN
DO NOT REMOVE THIS LABEL
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT
INSTALLATION AND RESTRICTIONS IN YOUR AREA.
LISTED SOLID FUEL BURNING APPLIANCE SUITABLE FOR USE IN
RESIDENTIAL, ALCOVE AND MOBILE HOME INSTALLATIONS.
TESTED TO UL 1482
FREESTANDING INSTALLATION
DOUBLEWALL CONNECTORS
STANDARD RESIDENTIAL
INSTALLATION (SINGLEWALL CONNECTOR)
PATRIOT
18"
18"
10"
27"
19.25"
17.75"
FLOOR PROTECTOR
6" MIN.
6"
F
MIN.
STOVE
16" MIN.
C
U.S. ENVIRONMENTAL PROTECTION AGENCY
DATE OF MANUFACTURE
Jan.
Feb.
Mar.
Apr.
SERIAL
NUMBER
• GSW model Super Chimney Twenty-One connected directly to appliance
• SELKIRK METALBESTOS model DS connector with model SSII chimney
• ICC EXCEL (2100-2 Can.) (103-HT USA) chimney with HP connector
MOBILE HOME AND ALCOVE INSTALLATIONS
PARLOR
18"
18"
9.75"
27"
19.25"
17.75"
OPTIONAL EQUIPMENT: Rear Blower
Electrical rating: 115V, 60 Hz., 1.8 Amps
Replace glass only with LOPI supplied NEOCERAM
ceramic glass (5mm).
Manufactured By:
4800 Harbour Pointe Blvd. SW Mukilteo, WA 98275
May
June
July
Aug.
(DOUBLE WALL CONNECTOR)
PATRIOT
PARLOR
18"
18"
10.5"
10.5"
10"
9.75"
26.5"
26.5"
11.25"
11.25"
17.25"
17.25"
Sep.
Oct.
Nov.
Dec.
0469