F. Cut Out Hole in Roof
Refer to Figure 8.9.
Plumb from roof to center of chimney.
Drive a nail up through roof to mark center of pipe.
Measure to either side of nail and mark the 17 in. x 17 in.
(432 mm x 432 mm) opening required.
Measure opening on the horizontal; actual length may be
larger depending on roof pitch.
Cut out and frame opening.
Refer to Chapter 25 of the Uniform Building Code for
roof framing details.
G. Complete Installation
WARNING! Risk of Fire! You MUST maintain 2 in.
(51 mm) air space to insulation and other combustible ma-
terials around the chimney system. Failure to do so could
cause overheating and fi re.
Keep chimney sections from separating or twisting.
You may secure straight chimney sections at the joints
with screws no longer than 1/2 in. (13 mm).
H. Install Flashing
Slip the fl ashing over the chimney.
Nail the fl ashing to the roof. Keep gaps between fl ashing
plate and roof to a minimum.
NOTICE: Roofi ng shingles must be below the fl ashing
plate on the lower side of a sloped roof and over the
fl ashing plate on the sides and top.
Caulk the fl ashing plate and roof junction as well as the
vertical seam on the fl ashing. All nail heads must be
caulked with a roofi ng sealant.
30
Heat & Glo • RUTHERFORD-36 • 4059-341 Rev D • 03/09
Figure 8.9
Ceiling/Attic Construction