3. Locations to be Avoided
In the garage. Products of combustion are present when you start your car. Only a Heat
Alarm is suitable in such locations
In front of forced air supply ducts used for heating and air conditioning, near ceiling fans, or
other high air flow areas.
Less than 10cm (4") from the peak of an 'A' frame type ceiling.
In an area where the temperature may fall below 0°C or rise above 40°C. Such as garages
and unfinished attics; this should also include electrical boxes exposed to these environ-
ments..
In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.
In very humid areas. Moisture or steam can cause nuisance alarms.
In areas where the Relative Humidity (RH) is above 93%.
Near fluorescent lights or CFL lamps.. Electronic "noise" may cause nuisance alarms.
In insect infested areas
Smoke alarms should not be installed within 0.9m (3ft) of the following: the door to a
kitchen,the door to a bathroom containing a tub or shower, ceiling or whole house ventilat-
ing fans orother high air flow areas..
Kitchens: Normal cooking may cause nuisance alarms. Only Heat Alarms are suitable for
use in Kitchens; they should also be fitted in integral garages.
Smoke alarms are not to be used with detector guards unless the combination (alarm and-
guard) has been evaluated and found suitable for that purpose.

4. Installing Alarm

These are mains powered alarms, so isolate the mains supply before commencing instal-
lation. They are for installation by a qualified electrician in accordance with the
current I.E.E. regulations.
Select suitable location having regard to earlier advice.
Bring house wiring through a dry lining box into back of alarm; side entry, via mini
trunking is also possible by carefully knibbling away edge on trim-plate. Make good
joint, with white sealant, if necessary.
If alarm is not being interconnected, interconnect cable terminal (I/O) on alarm is unused.
a