Download Print this page
Greenheck SSFSDR-512 Specification Sheet
Greenheck SSFSDR-512 Specification Sheet

Greenheck SSFSDR-512 Specification Sheet

Combination fire smoke dampers round stainless steel blade

Advertisement

Quick Links

Application
Model SSFSDR-512 is a combination fire smoke damper constructed
out of 304 stainless steel with 3 round style blade. The SSFSDR-512
has been qualified to 3000 fpm (15.2 m/s) and 4 in. wg (1 kPa) for
operation and dynamic closure in emergency fire smoke situations.
Model SSFSDR-512 may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 Hour
Dynamic Closure Rating: Actual ratings are size dependant
Maximum Velocity: 3000 fpm (15.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
UL 555S Leakage Rating
Leakage Class:
Operational Rating:
Maximum Velocity:
Maximum Pressure:
Maximum Temperature:
Standard Construction
Frame/Sleeve: 20 ga. (1mm) 304 stainless steel round
Blades: Double skin 304 stainless steel (14 ga.
Seals: Extruded silicone rubber blade seals
Linkage: 304 stainless steel - concealed in jamb.
Axles: 1/2 in. (13mm) dia. 304 stainless steel.
Bearings: 304 stainless steel sleeve type
Fusible Link: UL listed 165ºF (74ºC) -not 304SS
Size Limitations
Minimum Size: 6 in. (152mm) diameter
Maximum Size: 24 in. (610mm) diameter
Optional Features
• OCI (Open closed indication switches) -not 304SS
• 165º F (74°C), 212º F (100°C), and 350º F (177°C) RRL available
- not 304SS.
• TOR (remote override of 165º F (74°C) closure allows damper to
perform smoke management functions during a fire emergency)
- not 304SS.
• Electric or pneumatic actuators to accomplish smoke management
and system functions.
• One retainer plate required, additional retainer plate available.
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve
Minimum Wall/Floor Opening
= Nominal Dia. + 7/8 in.
1.00 in. Min. Typ.
II
Actual ratings are actuator dependant
3000 fpm (15.2 m/s)
4 in. wg (1 kPa)
350º F (177°C) —Depending on actuator
integral sleeve
[2mm] equivalent) round style blades
Opening + 2 in. Min.
Clamping
Screw
Fasteners
Nut
Combination Fire Smoke Dampers
UL 555 1 1/2 Hour Fire Resistance Rating
Model SSFSDR-512 meets the requirements for
fire dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshall
Listing #: 3225-0981:112 (fire)
Listing #: 3230-0981:113 (smoke)
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards
(see complete marking on product)"
Standard 555 (Listing #R13317)
Standard 555S (Listing #R13447)
Minimum Wall/Floor Opening
* Dimensions furnished approximately 1/8 in. (3mm) undersize.
= Nominal Dia. + 7/8 in.
Installation instructions available at www.greenheck.com.
1.00 in. Min. Typ.
SSFSDR-512
Round Stainless Steel Blade
UL 555S Leakage Class II
Opening + 2 in. Min.
Clamping
Screw
Fasteners
Nut
Retaining
Plate Assembly
Clamping Screw
D*

Advertisement

loading

Summary of Contents for Greenheck SSFSDR-512

  • Page 1 Application Model SSFSDR-512 is a combination fire smoke damper constructed out of 304 stainless steel with 3 round style blade. The SSFSDR-512 has been qualified to 3000 fpm (15.2 m/s) and 4 in. wg (1 kPa) for operation and dynamic closure in emergency fire smoke situations.
  • Page 2 AMCA certified ratings program for test figures 5.2, 5.3, and 5.5. Damper air performance data shall be developed in accordance with the latest edition of AMCA Standard 500-D. Basis of design is Greenheck’s model SSFSDR-512 OPTIONAL BLADE POSITION INDICATOR AND/OR ELECTRIC LINK.