Download Print this page

Dimensional Data - Greenheck DFD-150X series Specification Sheet

Greenheck dynamic rated fire dampers specification sheet

Advertisement

DFD-150X Type A
Dampers larger than maximum single section size are supplied in 2 or more sections of equal size.
The following chart and illustrations show minimum and maximum damper section size and assembly configurations for
multi-section dampers.
SIZE LIMITATIONS
Type A
Inches
(mm)
minimum
maximum
Single
6 x 4
36 x 36
Section
(152 x 102)
(914 x 914)
Vertical
72 x 48
Multi
(1829 x 1219)
Section**
NA
or
Vertical
60 x 60
(1824 x 1524)
Single
6 x 4
30 x 30
Section
(152 x 102)
(762 x 762)
Horizontal
Multi
48 x 36
Section**
NA
(1219 x 914)
Horizontal
Installation of sizes larger than the maximums shown requires approval of
the authority having jurisdiction.
** Consult factory for number of sections.
1
MAXIMUM SINGLE
SECTION DIMENSIONS
36in. max.
(914mm)
2
MULTI-SECTION LIMITATIONS
Maximum height is 48 in. (1219mm) when width is 72 in.
(1829mm) or less.
48 in. (1219mm) max.
Type B
minimum
maximum
6 x 6
36 x 32
(152 x 152)
(914 x 813)
72 x 45
(1829 x 1143)
NA
or
60 x 56
(1524 x 1422)
6 x 6
30 x 26
(152 x 152)
(762 x 660)
48 x 32
NA
(1219 x 813)
36 in. max.
(914mm)
72 in. (1829mm) max.
Blade Stack

Dimensional Data

H*
in.
mm
8
203
9
229
10
254
11
279
12
305
13
330
14
356
15
381
16
406
17
432
18
457
19/37/38
483/940/965
20/39/40
508/991/1016
21/41/42
533/1041/1067
22/43/44
559/1092/1118
23/45/46
584/1143/1168
24/47/48
610/1194/1219
25/49/50
635/1245/1270
26/51/52
660/1295/1321
27/53/54
686/1346/1372
28/55/56
711/1397/1422
29/57/58
737/1448/1473
30/59/60
762/1499/1524
31/32
787/813
33/34
838/864
35
889
36
914
*
These dimensions are furnished
approximately
/
in. (6mm) undersize.
1
4
P
H*
W *
P
in.
mm
1.2
30
1.3
33
1.3
33
1.4
36
1.6
41
1.7
43
1.8
46
1.8
46
2.0
51
2.1
53
2.2
56
2.3
58
2.4
61
2.6
66
2.6
66
2.7
69
2.9
74
3.1
79
3.2
81
3.2
81
3.3
84
3.4
86
3.6
91
3.7
94
3.9
99
4.1
104
4.2
107

Advertisement