Specifications - GE Digital Energy GT6000 User Manual

Gt series ups 6 - 10 kva
Table of Contents

Advertisement

9

SPECIFICATIONS

Model
Ratings
Voltage Amperes (VA) with computer type load
Watts (W) with resistive load
Input thermal circuit breaker (A)
Internal input fuse 250V, slow (A)
Input converter
AC input voltage
AC input voltage range
Input current waveform
Input current (A) at nominal input voltage
Input power factor
Input frequency range
Inrush current
Output converter
AC output voltage
AC output voltage tolerance
Output frequency
Output frequency range
Output waveform
Harmonic distortion
Power factor
Crest factor (peak to RMS current)
Capacity appliance outlets
Bypass
AC input voltage range
Frequency tracking rate
Frequency tracking range
Typical transfer time, msec
Overload capability
Overload behaviour during battery operation
Overload behaviour during bypass operation
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc)
Number / Ah batteries (in battery kit and battery ext. pack) :
Type
Service life
Recharge current
Battery recharge time
(batt. discharged at 100% load)
Runtime in minutes
at typical load (75%)
%
VA/Watts
25%
1500/1050
50%
3000/2100
75%
4500/3150
100% 6000/4200
%
VA/Watts
25%
2500/1750
50%
5000/3500
75%
7500/5250
100% 10000/7000
General
Weight UPS kg
Dimensions UPS (h
w
d)
x
x
Weight battery pack kg
Dimensions battery pack
Enclosure / protection
Environment
Safety
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
Max. relative humidity
Colour
modifications reserved
:
GT6000
:
6000
:
4200
:
30
:
30
: Nominal: 230 V
: 84 - 276 V (84-175V with load de-rating)
input >276 Vac: UPS switches to battery operation
: sine wave
:
20.6
: > 0.97
: 40 - 70 Hz
: 60A
: 220 / 230 / 240 V (selectable)
: ± 2%
: 50/60 Hz, auto selection
: nominal ± 5% with mains synchronizing
: sine wave
: < 3% with linear load, < 8% with non-linear full load
: 0.7
: ≤3:1
: with 55A Terminal Block
: ± 10% of selected output voltage
: 1Hz/s
: ± 5% of selected frequency
: 0.5
: fully protected against overload and short circuits
: 125% during 1 minute
: 150% during 10 seconds
: depends on rating of thermal circuit breaker
typical:
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
:
240
20pcs / 8Ah
: sealed lead acid, maintenance free
: up to 5 years (depending on use)
: 1.2 A
: 5 hours for 90% capacity
:
17
:
66
:
28
:
17
:
12
:
:
:
:
:
-
: 24.5
: 130x410x660mm
: 67
: 130x410x660mm
: steel-plastic / IP20
: EN 62040-1
: EN 62040-2 (2006)
: 0 to +40ºC
: < 55 dB(A), load and temperature dependent
: 90% (non-condensing)
: Black - RAL 9005
25
GT10000
10000
7000
63
30*2
34.6
240
20pcs / 8Ah
9
37
15
9
5
User manual GT Series 6 - 10 kVA UPS 1.0 (GB)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Digital energy gt10000

Table of Contents