SPECIAL NOTE: Systems with MORE than 15' of
interconnecting tubing, please refer to Table 5 for line
charge allowance per foot of tubing.
LINE CHARGE ALLOWANCE (R-22) (oz./ft.)
LINE
O. D. (IN)
1/4
3/8
1/2
5/8
3/4
7/8
1 1/8
1 3/8
TABLE 5
IO-101G
LIQUID
SUCTION
LINE
LINE
0.22
0.58
1.14
1.86
0.04
0.06
0.08
0.15
0.22
NOTE: System with over 50' separation between
condensing unit and evaporator may require oil charge
adjustment.
OIL CHARGE ADJUSTMENT
UNIT MODEL
ADDITIONAL OIL CHARGE PER EACH
(TONS)
1 - 1 1/2
2 - 5
*Use either Texaco WF-32 (formerly cappella B)
or Suniso 3G-S oil
6
ADDITIONAL 10' OF LINE (OZ.)*
0.25
0.5
TABLE 6
06/04