1744/1743
Users Manual
Voltage Dips and Swells
If the voltage passes the upper limit (V
+ 10%) or lower limit (V
– 10%), the
N
N
event is registered as a voltage swell or dip, respectively (thresholds are
adjustable in PQ Log).
The duration, time, and extreme value of the dip or swell is also recorded.
Heigth
110% Un
100% Un
90% Un
Depth
Duration
Duration
Time
Zeit
egb019.eps
Figure 16. Voltage Dips and Swells
Voltage Harmonics
Voltage harmonics are defined as voltage components that have a frequency
that is an integer multiple of the fundamental frequency of the line power
voltage. Logging function A records each individual voltage harmonic, up to
th
the 50
order. These values are averaged over the interval length defined in
PQ Log.