See notes 1, 2, 4, 11, 12, and 13 on the page following these figures.
Fig. 30 - - Dual Fuel Thermostat with Single- -Stage Furnace
and Single- -Speed Heat Pump
Fig. 32 - - Two Stage Thermostat with Single- -Stage Furnace and Two- -Speed Air Conditioner
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
4. Dip switch No. 1 on humidity sensing thermostat should be set in OFF position for air conditioner installations. This is factory default.
5. Dip switch No. 1 on humidity sensing thermostat should be set in ON position for heat pump installations.
6. Dip switch No. 2 on humidity sensing thermostat should be set in OFF position for single- -speed compressor operation. This is factory
default.
7. Dip switch No. 2 on humidity sensing thermostat should be set in ON position for two- -speed compressor operation.
8. Configuration Option No. 10 "Dual Fuel Selection" must be turned ON in all dual fuel applications.
9. NO connection should be made to the furnace HUM terminal when using a humidity sensing thermostat.
10. The RVS Sensing terminal "L" should not be connected. This is internally used to sense defrost operation.
11. DO NOT SELECT the "FURNACE INTERFACE" or "BALANCE POINT" option on the two- -speed heat pump control board. This
is controlled internally by the humidity sensing thermostat/Dual Fuel Thermostat.
12. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single- -speed compressor operation. This is factory default.
13. Dip switch D on Dual Fuel Thermostat should be set in ON position for two- -speed compressor operation.
HUMIDFIER
(24VAC)
A04219
See note 2 on the page following these figures.
NOTES FOR FIGURES 26 - - 32
See notes 1, 2, 3, 4, 11, 12, and 14 on the page following these figures.
Fig. 31 - - Dual Fuel Thermostat with Single- -Stage Furnace
and Two- -Speed Heat Pump
HUMIDFIER
(24VAC)
24
HUMIDFIER
(24VAC)
A04220
A04221