Load Application - MULTIQUIP Power DCA10SPX3 Operation And Parts Manual

60 hz generator (kubota d1403 diesel engine)
Table of Contents

Advertisement

Single Phase, Load
Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage and
frequency requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require 130—
150% more wattage than the rating on the nameplate, as
the wattage is influenced by the efficiency, power factor and
starting system of the equipment.
If wattage is not given on the
equipment's name plate, approximate
wattage may be determined by
multiplying nameplate voltage by the
nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 1.0. See Table 10.
below when connecting loads.
T
b a
e l
1
. 0
o P
y T
e p
f O
o L
d a
i S
g n
e l
p -
a h
e s
n i
u d
i t c
n o
m
E
e l
t c
c i r
h
a e
e t
, s r
n i
a c
d n
s e
a l
m
s p
F
u l
r o
s e
e c
t n
a l
m
p
, s
m
r e
u c
E
e l
r t c
n o
c i
d
i v e
e c
, s
o c
m
m
e
u q
p i
m
e
t n
CAUTION:
Motors and motor-driven equipment draw
much greater current for starting than during
operation.
When connecting ordinary power tools, a capacity of up to
the generating set's rated output (kW) multiplied by 0.8 can
be used.
PAGE 34 — DCA-10SPX3 A.C. GENERATOR— PARTS & OPERATION MANUAL — REV. #2 (01/17/11)
NOTE
w
r e
a F
t c
r o
B
y
o L
d a
o P
w
r e
a F
o
o t
s r
. 0
- 4
. 0
e c
t n
1
0 .
y r
a l
m
s p
. 0
- 4
0
n u
c i
i t a
n o
1
0 .
DCA-10SPX3 — LOAD APPLICATION
An inadequate size connecting cable which cannot carry
the required load can cause a voltage drop which can burn
out the appliance or tool and overheat the cable.
● When connecting a resistance load such as an
incandescent lamp or electric heater, a capacity of up
to the generating set's rated output (kW) can be used.
● When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set's rated output (kW)
multiplied by 0.6 can be used.
● When connecting an electric drill or other power tools,
pay close attention to the required starting current
capacity.