Multi-vendor Use

Connecting a Non-OMRON Configurator
This section describes how to connect OMRON Slaves to a non-OMRON Master.
Do not perform communications with a bit strobe connection for Slaves that have outputs. DeviceNet
I/O communications have multiple connection types, such as poll and bit strobe, but for DeviceNet
specifications, bit strobe connections are used for inputs only. Following these specifications, OMRON
Master Units communicate with output Slaves by using a poll connection.
Some non-OMRON Masters perform communications with output units by using a bit strobe
connection. Check the specifications before performing connections when connecting with a non-
OMRON Master.
When connecting an OMRON Slave to a non-OMRON Master, it is necessary to install the OMRON
Slave's EDS file in the non-OMRON Configurator, and set the Slave data in the Master. (Some non-
OMRON Masters can be connected with performing this setting.) In addition to enabling connection to
non-OMRON Masters, installing the EDS file in the Configurator also enables setting specific
parameters for each Slave by using the Configurator.
If the EDS file cannot be obtained or the non-OMRON Configurator does not support EDS files, you must directly input
the connection type and the data size.
The EDS file uses default settings (i.e., mode switch 0). To use other settings, change the connection type, data size,
and connection pathe for the set mode.
For details, refer to Object Implementation in this section.
Refer to the following devices profiles if more detailed DeviceNet specifications for Slaves are required
when registering the scan list.
Device Profiles
General data
Physical
conformance
data
Communications
data
RFID System
144
User's Manual
p.148 to p.149
Applicable DeviceNet
specifications
Vendor name
Device profile name
Product catalog number
Product revision
Network power consumption
Connector type
Physical layer insulation
Support indicator
MAC ID setting
Default MAC ID
Transmission baud rate setting
Supported transmission baud rates 125, 250, or 500 kbps
Predefined Master/Slave
connection set
Dynamic connection support
(UCOMM)
Explicit message fragmentation
support
Volume 1 Edition 3.1
Volume 3 Edition 1.3
OMRON Corporation
Slave: Generic
Manual number
2.1
24 VDC, 40 mA max.
Open flag
Yes
Module
Network
Set with software or rotary switches (software setting numbers 64 to 99)
0
No (baud rate recognized automatically)
Group 2 only server
No
Yes
Vendor ID = 47
Profile number = 0