Rear Vent Through-The-Wall Installations; Rear Vent Venting Runs; Heat Shields - Montigo Homefire ME34-DV-2 Installation & Operation Manual

Modular gas fireplace
Hide thumbs Also See for Homefire ME34-DV-2:
Table of Contents

Advertisement

Rear Vent Venting Runs

A. Simple Rear Vent Installations
The ME34-DV-2 Rear Vent has three possible installations which do
not require vertical lift:
1. Straight Installation.
The height from the hearth to the center of the termination is 26
1/8". ME34-DV-2 Rear Vent versions are supplied with an 18"
extension pipe (EXT-18) with female/female connections. For
shorter installations, cut the EXT-18 to the desired length.
For extended installations, use the EXT-18 section as supplied for
an 18" vent run.
For Rear Vent models, maximum horizontal run with no
Note:
vertical lift must never exceed 18".
Heat Shield
EXT-18
Flue Collar
Figure 15. Extended installation.
Part No. XG0105B
Installation
Termination
Rear Vent
2. 45° Corner Installation.
Attach an EEL-45 (45° elbow) directly onto the flue collar. Cut the
EXT-18 to suit, and attach it to the EEL-45. Slide the fireplace into
position and attach to the termination.
Figure 16. Corner installation.
3. Corner Installation - 45° or less.
Use an MTO-3 termination and an MFL-1 or MFL-18 (12" or 18"
compressed length) and a frame, if appropriate. Flex may be
turned to obtain desired degree of angle required but must not
exceed 45°.
Figure 17. Flex installation.

Heat Shields

Due to high flue temperatures, heat shields are required on all ME34-
DV-2 installations (except those with vertical terminations) at the point
where the venting connects to the termination. With the heat shield,
vent clearances can be maintained at 1".
See Figure 8.
ME34-DV-2 Homefire
Termination
Heat Shield
EXT-18
EEL-45
Elbow
Flue Collar
Termination
Heat Shield
Flex
Section
Flue Collar