Water-Cooled Condenser; A) Connection To An Open Drain System - Hoshizaki KMD-850MAH Instruction Manual

Modular crescent cuber
Hide thumbs Also See for KMD-850MAH:
Table of Contents

Advertisement

2. Water-Cooled Condenser

a) Connection to an Open Drain System

Condenser Water
Minimum Condenser
Supply Inlet
Water Supply Line Size
1/2" Female Pipe
1/4" Nominal ID Copper
Thread (FPT)
Water Tubing or Equivalent
• A condenser water supply line shut-off valve and drain valve must be installed.
• In some areas, a back flow preventer may be required in the cooling water circuit.
• In order to maintain the proper high side pressure, the condenser water supply inlet
temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature
must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation
is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze
cycle starts. If the condenser drain outlet temperature is not in the proper range, use a
flat blade screwdriver to rotate the adjustment screw on the water-regulating valve until
the temperature is in the proper range (rotate counterclockwise to raise temperature or
clockwise to lower temperature).
Icemaker Water
Supply Inlet
1/2" FPT
Condenser Water
Supply Inlet
1/2" FPT
Condenser
Drain Outlet
3/8" FPT
Vent Tube
Icemaker
Condensation
Drain Outlet
5/8" OD Hard
Tube
Icemaker
Drain Outlet
3/4" FPT
Vent Tube
Bin Drain Outlet
3/4" FPT
Minimum 1/4"
Nominal ID Hard
Pipe or Equivalent
Minimum 3/4" Nominal ID
Hard Pipe or Equivalent
Fig. 5
Model Shown:
Connection to an Open Drain System
KMD-901MWH
Icemaker
Ice
Storage
Bin
Water-Cooled Models
Condenser Drain
Minimum Condenser
Outlet
Drain Line Size
3/8" Female Pipe
1/4" Nominal ID Hard Pipe
Thread (FPT)
or Equivalent
Minimum 1/4" Nominal ID Copper
Water Tubing or Equivalent
Shut-Off
Valve
Drain Valve
18
Minimum 1/4" Nominal ID Copper
Water Tubing or Equivalent
Be sure there is sufficient
extra water supply line and
drain line for the appliance
to be pulled out for service.
Separate piping to approved
drain. Leave a 2-inch (5-cm)
vertical air gap between the
end of each pipe and the
drain.
2-inch (5-cm) air gap
Floor Drain