LonWorks interface
6.4

Output network variables

Function
Node Object status
Drive speed feedback
Actual motor current
Actual drive power
Drive total running
hours
Status word
kWh trip counter
Active fault code
Process Out
Digital Out
Parameter Out
NvoStatus
This output network variable reports the status for Node object or Variable Speed Motor Drive
object.
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal
speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
Variable Name
nvoStatus
nvoDrvSpeed
nvoDrvCurnt
nvoDrvPwr
nvoDrvRunHours
nvoDrvStatus
nvoDrvEnrgy
nvoActFault
nvoProcessOut1..8
nvoDigitalOut1..8
nvoParResp
Table 13. Output network variables
Field
object_id
invalid_id
invalid_request
disabled
electrical_fault
in_alarm
report_mask
SNVT Type
SNVT_obj_status
SNVT_lev_percent
SNVT_amp
SNVT_power_kilo
SNVT_time_hour
SNVT_state
SNVT_elect_kwh
SNVT_count
SNVT_
lev_percent
SNVT_switch
SNVT_preset
Description
ID of object within node
1 means requested ID is not
implemented in this node
1 means request for unimple-
mented function
1 means object disabled
1 means drive is faulted
1 means drive is in alarm
1 means status is an event mask
Table 14.
Honeywell • 21
Min. Value
Max. Value
-163.840%
+163.830%
0.0A
3276.7A
0,0 kW
6553,5 kW
0 h
65535
n/a
n/az
0kWh
65535kWh
0
41
0
65535
0
4