7. The Start Time for Occupied 1 will be displayed. Use
the UP ARROW and DOWN ARROW buttons to raise
or lower the time until the desired Start Time is shown.
Press the Mode button to continue. See Fig. 6.
Fig. 6 — Start Time Display
8. The Stop Time for Occupied 1 will be displayed. Use
the UP ARROW and DOWN ARROW buttons to raise
or lower the time until the desired Stop Time is shown.
Press the Mode button to continue.
9. The On/Off icon will be displayed. Use the UP AR-
ROW to turn the Occupied 1 period ON for this day.
Use the DOWN ARROW to turn the Occupied 1 period
OFF for this day.
10. Repeat Steps 2 through 9 to program the remaining sched-
ule for Occupied periods 2 and 3.
11. The Copy command can be used to copy the previous
day's schedule if the schedules are the same. The copy
command becomes available after all the occupied pe-
riods are programmed in a day. Use the UP ARROW to
change the copy command to YES. Use the DOWN AR-
ROW to change the copy command to NO. Press the
Mode button when the choice has been made. See
Fig. 7.
If NO was selected, the schedule will automatically change
to the next day and the user must enter the occupied and
unoccupied schedules for that day.
NOTE: Occupied 1 schedule heating and cooling set points
are the same for each day. Occupied 2 and 3 set points
may be set to different values for each day of the week.
If YES was selected, the schedule will be copied to the
next day. The schedule copy may be repeated until Sun-
day is reached. The Sunday schedule cannot be copied
to Monday.
12. After all the times and set points for each day have been
entered, press the Program button to exit programming
mode.
NOTE: The thermostat will continue to follow the schedule
until a new one is entered.
Fig. 7 — Copy Command Display
If only one occupied schedule is selected, the Occupied 2
and 3 schedules are skipped. If the start time is set later in
the day than the stop time, the program will run from mid-
night of that day to the stop time and then from the start time
to midnight. If the same start and stop times are pro-
grammed for an occupancy schedule, the thermostat will be
in Occupied mode for 24 hours. If one occupied period starts
or stops within another occupied period, the lower num-
bered schedule has priority. For example, if schedule Oc-
cupied 3 is running for 24 hours and Occupied 2 schedule
comes on from 1 to 3 PM, the set points from Occupied 2
are in effect from 1 to 3 PM.
OVERRIDING THE SCHEDULE — The schedule can be
overridden by pressing the UP or DOWN ARROW buttons
to change the desired temperature. The thermostat will use
the new set point until the next scheduled time period starts.
Calibrate Sensor —
brated. Under normal circumstances there will never be a
need to re-calibrate the thermostat. If re-calibration must be
done, perform the following procedure:
1. Hold down the Mode and Fan buttons for 5 seconds. All
of the icons on the display screen will appear. Release the
buttons. Press the UP and DOWN ARROW buttons
simultaneously.
2. Press the UP and DOWN ARROW buttons simulta-
neously again. The current temperature will be
displayed.
3. Use an accurate thermometer to measure room tempera-
ture. Press the UP or DOWN ARROW buttons until the
number equals room temperature.
4. Press the Mode button to return to normal operation.
Check Thermostat Operation —
stat operation, perform the following procedure:
1. Press the Mode button repeatedly until the Heat icon ap-
pears on the display. The thermostat is now in Heating
mode.
2. Press the Fan button. The Fan Auto icon will appear on
the display screen. Press the UP ARROW button until the
heating set point is 10 F (6 C) higher than the current
room temperature. Heating and fan should be
energized.
3. Press the Mode button repeatedly until the Cool icon ap-
pears on the display. The thermostat is now in Cooling
mode.
4. Press the DOWN ARROW button until the cooling set
point is 10 F lower than the current room temperature.
Cooling and fan should be energized.
5. Press the Mode button repeatedly until the Off icon ap-
pears. Press the Fan button until the display reads Fan
On. The fan should energize.
6. If heating, cooling, or fan operation do not work, check
wiring and consult Table 4.

Final Checklist

1. Put away tools and instruments. Clean up debris and
packaging.
2. Review Owner's Guide with occupant or owner.
3. Leave the manuals with owner.
6