Table 2-10: Configuration > Other I/O & Groups > Inputs Tab Field Descriptions
Setting
Name
Mode
Shunt Time
Debounce Time
Time Zones
Auto-Relock
NetAXS™ Access Control Unit User's Guide, Document 800-00233, Revision A
Description
Enter a unique name to identify the device.
Normally Closed
– Specifies that the door's normal state is
closed.
– Specifies that the door's normal state is open.
Normally Open
Unsupervised
– Specifies that the door's electrical circuit is
wired in one path without alternative paths supervised by
resistors.
– Specifies that the door's electrical circuit is wired
Supervised
with alternative paths supervised by resistors.
Specifies the amount of time for which the inputs will be
shunted, or de-activated. For example, it specifies how long a
door strike will remain released. Enter the desired number of
hours (1024 maximum), minutes (60 maximum), and seconds
(60 maximum). The sum of all three units comprises the shunt
time. Note that you can express seconds in tenths of a second.
Specifies the period of time the input must remain in a new state
before generating an alarm. For example, if a Normal state is
changed to Alarm, the state must remain in Alarm for five
seconds before an alarm is generated.
Shunt
– Specifies the time period during which the input will be
energized.
– Specifies the time period during which the
Disable Interlock
programmed action on this input from another point will be
disabled.
– Specifies the time period during which
Disable Alarm Msgs
the input will generate no alarms.
Causes the door to re-lock immediately when the door status
switch closes after entry. The output relay that controls the door
strike de-energizes when the associated input returns to normal
state instead of remaining energized for the duration of the pulse
time. To enable Auto-Relock, de-select the
and select the associated output from the drop down list.
Configuring via the Web Server
Configuring Other I/O & Groups Tab
Disable
checkbox,
2-45