3.7.4 Auxiliary Power Configuration
Output circuits 1-4 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are:
Door Holder
Constant
Resettable
Sounder Sync Power
Auxiliary power circuits are power-limited. Each circuit can source up to 3A (total current for all output circuits must not exceed 6 A).
To configure an output circuit as auxiliary power, perfor the following steps.
1.
Wire the output circuit(s) that will be used for auxiliary power. See Figure 3.9 below for the location of the output circuits.
2.
Configure the auxiliary power output through programming for door holder, constant, resettable, or sync power.
.
Door Holder Power
Door holder is intended for use with fire door applications. When there are no alarms in the system and the panel has AC power, the door
holder circuits have 24-volt power present at their terminals. Any alarm will cause the power to discontinue. The Power will be re-applied
when the system is reset. If the AC power is off for more than 15 seconds, the auxiliary door holder power will be discontinued to conserve
the battery backup power. When AC power is restored, power is immediately restored to the door holder circuits.
Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
Resettable Power
Resettable power is typically used to power beam detectors, flame detectors, and conventional 4-wire smoke detectors. For circuits selected
as Resettable, 24VDC power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is removed from
the terminals for 30 seconds, then re-applied. The wiring class of the external power source must match the wiring class of the device being
powered. If extra power circuits are needed, a UL 864-listed, regulated, power-limited power supply with Class A aux power output must be
used.
Sounder Sync Power
Sounder sync power continuously outputs the System Sensor synchronization pattern and it is intended for use with the B200S Series
sounder bases.
14
1
2
B A T T E R Y
+
3
4
5
O U T 3
O U T 4
H 4 –
H 3 –
H 4 +
Figure 3.9 Output Circuits Used as Auxiliary Power
7
8
9
1 0
6
1 1
O U T 2
O U T 1
H 2 –
H 2 +
H 1 –
S –
H 3 +
H 1 +
+
-
5496 Intelligent Power Module Manual — P/N 151276-L8:F2 2/15/2022
Notification Appliance Wiring
1 2
1 3
1 4
S B U S
S +
A
B
power-limited
supervised when used with the Power
Supervision Relay (PN 160150)