5.3 Setpoint Ramp/Soak Programming

Introduction
Setpoint Ramp/Soak Programming lets you configure six ramp and six soak
segments to be stored for use as one program or several small programs. You
designate the beginning and end segments to determine where the program is to
start and stop.
Review program data and configuration
While the procedure for programming is straightforward, and aided by prompts,
we suggest you read "Program Contents". Table 5-2 lists the program contents
and an explanation of each to aid you in configuration. Then refer to Subsection
3.5 – Configuration to enable and configure the setpoint program.
NOTE: SPRATE and SPRAMP must be disabled to enable SP PROG (Set Point
Programming).
Fill out the worksheet
Refer to the example in Figure 5-1and draw a Ramp/Soak Profile on the
worksheet provided in Figure 5-2 and fill in the information for each segment.
This will give you a record of how the program was developed.
Operation
Refer to Table 5-3 Run/Monitor the program.
Program Contents
Table 5-2 lists all the program contents and a description of each.
Power outage
ATTENTION
be in hold and the setpoint value will be the setpoint value prior to the beginning
of the setpoint program. The program is placed in hold at the beginning. The
mode will be as configured under "PWR UP" in the "CONTROL" group.
4/00
If power is lost during a program, upon power-up the controller will
UDC2300 Universal Digital Controller User Manual