4.12 Setting a Failsafe Output Value for Restart After a Power Loss

Introduction
If the power to the controller fails and power is reapplied, the controller goes
through the power up tests, then goes to a user configured FAILSAFE OUTPUT
VALUE.
Set a Failsafe Value

Table 4-11 Procedure for Setting a Failsafe Value

Step
Operation
1
Select Control
Set-up Group
2
Select Failsafe
Function
Prompt
3
Select a value
4
Return to
Normal Display
4/00
Press
SET UP
Until you see:
Upper Display = SET
Lower Display = CONTRL
You will see:
FUNCTION
Upper Display = (range)
within the range of the Output 0 to 100 for all output
types except 3 Position Step
3 Position Step
Lower Display = FAILSF
[ ] [ ]
To select a Failsafe output value in the upper display
DISPLAY
At power up, the output will go to the value set.
UDC2300 Universal Digital Controller User Manual
Result
0 = motor goes to closed position
100 = motor goes to open position