Download Print this page

Special Features - Tripp Lite SmartOnline SU3000RTXL2U Specifications

Smartonline 3kva on-line double-conversion ups, 2u rack/tower, 100/110/115/120/127v, nema outlets
Hide thumbs Also See for SmartOnline SU3000RTXL2U:

Advertisement

UPS Shipping
22.9 x 55.9 x 83.3
dimensions (height x
width x depth / cm)
Shipping weight (lbs)
78.3
Shipping weight (kg)
35.5
Cooling method
Fan
UPS housing material
Steel
ENVIRONMENTAL
Operating
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Temperature Range
Storage Temperature
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Range
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr.
1000
(full load)
AC economy mode
241
BTU / hr. (full load)
Battery mode BTU /
1500
hr. (full load)
AC economy mode
97%
efficiency rating
(100% load)
COMMUNICATIONS
Communications
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
interface
Network monitoring
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
port description
communications
PowerAlert software
Included
Communications
USB and DB9 cabling included
cable
WatchDog
Supports Watchdog application, OS and hard-reboot restart options for remote applications
compatibility
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer
80V (100% load), 70V (66% load), 60V (33% load)
to battery power
(setpoint)
High voltage transfer
144
to battery power
(setpoint)

SPECIAL FEATURES

Cold Start (startup in
Cold-start operation supported
battery mode during
a power failure)
High availability UPS
Automatic inverter bypass; Hot swappable batteries
features

Advertisement

loading