Lennox Hearth Products MPD35ST-NM-B Installation Instructions Manual page 16

Merit plus series mpd35 direct-vent gas fireplaces
Table of Contents

Advertisement

Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of el-
bows required. Refer to Vertical Vent Figures
and Tables on page 15 to select the type of
vertical installation desired. Vent sections are
available in net lengths of 4-1/2" (114 mm),
10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"
(876 mm) and 46-1/2" (1181 mm). Refer to the
Effective Vent Length Chart on page 15 for an
aid in selecting length combinations. Elbows are
available in 90° and 45° configurations. Refer
to Figure 24 for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Where required, a telescopic vent section
(SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
has an effective length of from 1-1/2" (38 mm)
to 7-1/2" (191 mm). The SV4.5LA is fitted with
a locking inclined channel end (identical to a
normal vent section component) and a plain end
with 3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Maintain a minimum 1" (25 mm) clearance to
combustible materials for all vertical elements.
Clearances for all horizontal elements are 3"
(76 mm) on top, 1" (25 mm) on sides and 1"
(25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to locate
center of the vertical run. Cut and/or frame an
opening, 10-1/2" x 10-1/2" (267mm x 267mm)
inside dimensions, about this center mark
(Figure 20 ).
Figure 20
16
B. Attach vent components to appliance
- Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connections (see
Figures 21 and 22 ).
All of the appliances covered in this document
are fitted with collars having locking inclined
channels. The dimpled end of the vent com-
ponents fit over the appliance collar to create
the positive twist lock connection.
Figure 21
Arrow
Arrow
Figure 22
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlet of
the four inclined channels on the collar (refer to
10-1/2" Min.
(267 mm)
Figure 21). Push the vent component against
the collar until it fully engages, then twist the
component clockwise, running the dimples
down and along the incline channels until they
seat at the end of the channels. The unitized
design of the Secure Vent components will
10-1/2" Min.
engage and seal both the inner and outer pipe
(267 mm)
without the need for sealant or screws. If desired
a #6 x 1/2" screw may be used at the joint, but
it is not required as the pipe will securely lock
when twisted.
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner
as you would a vent section.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
First Vent
Component
Align the dimple (four places)
with the opening of the locking
incline channel on appliance
collar. Twist vent component
clockwise to engage and seal.
Dimple
Locking
Incline Channel
Appliance collar
Vent / Appliance Collar
Connection
Align the dimple (four places) of the
upper vent section with the opening of
the locking incline channel on the
lower vent section. Twist vent
component clockwise to engage and
seal until arrow and dimple align.
Dimple
Locking
Incline Channel
Connected
Vent Sections
Arrow
Vent / Vent Section
Connection
C. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vertical vent figures
and tables. To add another vent component
to a length of vent run, align the dimpled end
over the inclined channel end of the previously
installed section, adjusting the radial alignment
until the four locking dimples are aligned with
the inlets of the four incline channels of the
previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.This seating position
is indicated by the alignment of the arrow and
dimple as shown in Figure 22.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer
at ceiling joists; when using Secure Flex, use
SF4.5VF firestop/spacer. If there is living space
above the ceiling level, the firestop/spacer
must be installed on the bottom side of the
ceiling. If attic space is above the ceiling, the
firestop/spacer must be installed on the top side
of the joist. Route the vent sections through the
framed opening and secure the firestop/spacer
with 8d nails or other appropriate fasteners at
each corner. Remember to maintain 1" (25
mm) clearance to combustibles, framing
members, and attic or ceiling insulation
when running vertical chimney sections.
Attic insulation shield (96K94) may be used
to obtain the required clearances indicated
here. See installation accessories tables on
pages 37 and 38.
SV4.5CGV-1
SV4.5FA or
Termination
SV4.5FB Flashing
and SV4.5SC
Storm Collar
v
When
using
secure
Flex, use
v
Ceiling
SV4.5VF
Firestop/
Framing
Firestop / spacer
Spacer
SF4.5VF
u
SV4.5SP
Support Plate
u
SV4.5SU
Support Strap
Shown With
u
Optional
to Vent with
Radiant
Appropriate
Panels
Fasteners
Figure 23
1" (25.4 mm)
Minimum
Clearance to
Combustibles
8 ft. (2.4 M)
Maximum
Secured