System 10: Greenstar Heating Boiler With Zone Pumps And Room Thermostats - Bosch Greenstar 57 Manual

Gas combi/heating condensing boiler
Table of Contents

Advertisement

Applications Manual
2.10 System 10: Greenstar Heating Boiler with
zone pumps and room thermostats
Summary:
Single boiler with primary/secondary piping confi gura-
tion supplying multiple heating zones. Outdoor reset with
FW200 controller mounted on the boiler. 3rd party room
thermostats are used to communicate zone heat demands.
This system is identical to System 8 expanded to multiple
zones. The zone circulators run only when a heat demand
is communicated by the room thermostat and shut off
when the heat demand goes away.
Primary/secondary piping isolates the system fl ow from
the boiler fl ow and prevents the system from infl uencing
boiler performance.
This system works particularly well for installations with
other heat sources, e.g. wood stoves or signifi cant solar
gain. Compared to systems with the FW200 installed in the
room that will throttle down the boiler output when the
room reaches its set point, in this setup the thermostat
will shut the boiler off.
This system can also be used with a combi boiler (see
system 6) instead of the indirect fi red DHW tank.
In detail:
This system runs on pure outdoor reset without room
feedback on the heating curve. The FW200 installed in the
boiler adjusts the heating curve (boiler supply tempera-
ture) according to outdoor temperature. The 3rd party
room thermostats turn the boiler on and off based on the
conditions in the living space.
FW200 provides warm weather shutdown.
For temperature sensitive radiant fl oor applications install
a thermostatic tempering valve for overheat protection.
Bosch Thermotechnology Corp.
Required components:
Greenstar heating boiler.
FW200 controller in the boiler.
Primary/secondary piping and system pump.
Thermostatic mixing vavle (optional - overheat
protection for temperature sensitive floors).
3rd party room thermostats with dry contact closure
in each zone.
Indirect Fired DHW Tank.
Tank loading pump of suffi cient capacity.
Additional instructions:
See manufacturer's installation and operating instructions.
Bosch Greenstar | 49