7. INSTALLATION INSTRUCTIONS
Recommended Wire Length and Wire Diameter for Power Supply System
Models
C1852, CL1852
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of "A", "B".
AWG = American Wire Gauge
NOTE
To access the electrical component box,
open the air intake grille and remove the
electrical component box cover.
Wiring System Diagram
Single-phase
60 Hz, 230 / 208 V
Conduit's trade size for this unit is 1/2".
The conduit can be purchased at a hard-
ware store.
The fuse located in the outdoor unit pro-
vides power supply protection and may
blow when power is applied if the system
has been incorrectly wired.
(1) Ground the unit in accordance with local
codes.
(2) Be sure to size each wire allowing sev-
eral inches longer than the required
length for wiring.
(3) Use lock nuts to secure the conduit
tubes.
(A)
*1
Power Supply
AWG #12
75 ft.
Be sure to comply with
local codes while run-
ning the wire from the
indoor unit to the out-
door unit (size of wire
and wiring method,
etc.).
Every wire must be
connected firmly.
No wire should be
allowed to touch refrig-
erant tubing, the com-
pressor or any moving
part.
Time Delay
(B)
*1
Inter-unit
Fuse or
Wiring
Circuit
Capacity
AWG #12
65 ft.
15 A
INDOOR
INDOOR UNIT
1
2
3
Disconnect
switch
(Field supply)
G
CAUTION
– 21 –
Power Supply Terminal Base
(Outdoor Unit)
Max. Wire
Capacity
Diameter
20 A
AWG #12
OUTDOOR UNIT
(Inter-unit)
Power lines
B
230/208 V
1
Fuse
230/208 V
2
230/208 V
3
4
L1
5
L2
6
G
Grounding
line
Fig. 7
To avoid the risk of
electric shock, each air
conditioner unit must
be grounded.
Be sure to connect the
power supply line to
the outdoor unit as
shown in the wiring
diagram. The indoor
unit draws its power
from the outdoor unit.
A
1823_M_I
SM830079