Performing leak test & insulation
Pipe
Pipe size
Ø6.35 ~ Ø9.52
Liquid
pipe
Ø12.7 ~ Ø19.05
Ø6.35
Ø9.52
Gas
Ø12.70
pipe
Ø15.88
Ø19.05
Drainpipe and drain hose installation
Care must be taken when installing the drain hose for the indoor unit to ensure that any conden-
sate water is correctly drained outside.
The drain hose can be installed to the right of the base pan.
1
Insert the flexible hose to the drain hose port.
Fix the flexible hose to the indoor unit with the supplied cable clamp
•
securely. (Use the screwdriver to fix the flexible hose securely.)
2
Install the drain hose so that its length can be as short as possible.
Internal diameter of the drain hose should be the same or slightly bigger than the external diameter
of the drain hose port.
• Inner diameter of the drain hose
• Give a slightly slant to the drain hose for proper drainage of
condensate.
• Fix the flexible hose to the PVC with the supplied cable tie
securely.
3
Wrap the drain hose with the insulation drain as shown in figure and secure it.
24
INV HSP MA DUCT_DB98-33882A.indd 24
Insulation Type (Heating/Cooling)
Standard [30°C, 85%]
EPDM, NBR
9t
13t
13t
19t
32mm(Inner diameter)
High humidity [30°C, over 85%]
9t
13t
19t
25t
Remarks
Internal temperature is
higher than 120°C
Cable-tie
Clamp
Flexible hose
Insulation drain hose
Insulation cover drain