Installation To Solid Concrete Or Cinder Block - Westinghouse MT150 THIN Installation And Assembly Manual

Universal flat wall mount for 37" - 47" flat panel screens

Advertisement

Installation to Solid Concrete or Cinder Block

• When installing Westinghouse wall mounts on cinder block, verify that you have a minimum of 1-3/8" of actual con-
crete thickness in the hole to be used for the concrete anchors. Do not drill into mortar joints! Be sure to mount in a
solid part of the block, generally 1" minimum from the side of the block. Cinder block must meet ASTM C-90 specifica-
tions. It is suggested that a standard electric drill on slow setting is used to drill the hole instead of a hammer drill to
avoid breaking out the back of the hole when entering a void or cavity.
• Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete anchor.
• Make sure that the supporting surface will safely support the combined load of the equipment and all attached hard-
ware and components.
Make sure that wall plate (AA) is level, use it as a
1
template to mark four mounting holes. The top
mounting hole should be 2.5" above the desired
screen center as shown in figure 1.1 on page 4. Drill
four 1/4" (6 mm) dia. holes to a minimum depth of
2.5" (64 mm). Insert anchors (DD) in holes flush with
wall as shown (right). Place wall plate over anchors
and secure with #14 x 2.5" screws (CC). Level, then
tighten all fasteners.
WARNING
• Tighten screws so that wall plate is firmly attached,
but do not overtighten. Overtightening can damage
screws, greatly reducing their holding power.
• Never tighten in excess of 80 in. • lb (9 N.M.).
WARNING
• Always attach concrete expansion anchors directly to
load-bearing concrete.
• Never attach concrete expansion anchors to concrete
covered with plaster, drywall, or other finishing mate-
rial. If mounting to concrete surfaces covered with a
finishing surface is unavoidable, the finishing surface
must be counterbored as shown below. Be sure
concrete anchors do not pull away from concrete
when tightening screws. If plaster/drywall is thicker
than 5/8", custom fasteners must be supplied by
installer.
INCORRECT
wall plate
plaster/
dry wall
CORRECT
concrete
wall plate
plaster/
dry wall
WARNING
1
Drill holes and insert anchors (EE).
2
Place plate (AA) over anchors (DD) and secure with screws (CC).
3
Tighten all fasteners.
AA
CC
concrete
6 of 9
concrete
surface
DD
AA
DD
CC
DD
ISSUED: 02-08-06 SHEET #: 202-9092-1