Operating Conditions – All Models
Parameter
Ambient Temperature *
Humidity
% RH
Maximum Allowable
Working Pressure (MAWP)
Vacuum Region - Minimum
Pressure
mmHg absolute
Supply Voltage, Current,
and Load Resistance
* Ambient Temperature Limit is a function of Process Interface Temperature. (See Figure 13.)

Specifications

Reference Condition
Rated Condition
°C
°F
°C
25 ±1
77 ±2
10 to 55
MAWP is minimum of Body Rating or Seal Rating (See Model Selection Guide for Seal
MAWP)
Body
STR12D
STR13D
STR12D
STR13D
STR14G
STR17G
STR14A
Atmospheric (See Figure 15 for vacuum limitations.)
Voltage Range:
10.8 to 42.4 Vdc at terminals
Current Range:
3.0 to 21.8 mA
Load Resistance:
0 to 1440 ohms (as shown in Figure 16)
Operative Limits
°F
°C
0 to 100
0 to 100
MAWP
2500 psig (172 bar) Bolted Process Heads Table I _ _ A
2500 psig (172 bar) Bolted Process Heads Table I _ _ A
1450 psig (100 bar) All Welded Process Heads Table I _ _ C
1450 psig (100 bar) All Welded Process Heads Table I _ _ C
500 psig (35 bar)
3000psig (207 bar)
500 psia (35 bar).
34-ST-03-64