Condensate Drain Piping
Condensate Drain Piping
1. The drain hose should run straight
down the wall to a level where the
run off will not stain the wall.
2. These should have water traps.
Avoid putting the end of the hose in
water.
3. To conveniently drain the system,
the drain piping must slant
downward, with a slope of at least
1:50 to prevent leakage.
10
4. When the drain hose is placed in
the room, insulate the hose with
foam polyethylene to avoid damage
to the ceiling or furniture.
5. After completing installation of
refrigerant lines, wiring and drain
connections, bind the tubing,
wiring and drain piping (check if
local codes permit binding) into a
bundle by using tape at 100 or 200
mm (4" to 8") intervals. Make sure
the drain tube is at the bottom of
the bundle (Figure 16).
P.V.C. Tape
Insulation Tube
Suction Line Tube
Liquid Line Tube
Water Condensated
Drain Tube
Control Wiring
(P.V.C. Tube)
Power Wiring with
Ground Wiring
Figure 16