From - Viessmann Vitodens 100-W Compact Domestic Product Manual

Hide thumbs Also See for Vitodens 100-W Compact:
Table of Contents

Advertisement

Flue termination position
Position
A
Directly below an openable window, air vent or any other ventilation opening
B
Below a gutter, drain or soil pipe
C
Below eaves
D
Below a balcony
E
From vertical drain or soil pipes
F
From internal and external corners
G
Above adjacent ground or balcony level/roof
From a surface facing the terminal
H
I
Facing terminals
J
From opening door/window in carport into dwelling
K
Vertically from a terminal on same wall
L
Horizontally from a terminal on same wall
Adjacent to opening
M
N
Below carport/roof
O
From adjacent wall
From adjacent opening window
P
Q
From another terminal
R
Min. height
S
Min. distance measured perpendicular to roof covering
Flue terminal location for standard boilers
A
G
D,N
F
J
H,I
Additional requirements for condensing boilers
Minimum distance from terminal
2.5m
Boundary
C
B,C
B,C
L
K
K
M
K
K
E
F
A
F
G
G
Not under a car port
7
for standard boilers
L
P
R
Avoid access routes and patios
4
2.1m
Walkway
or patio
Minimum spacing
for condensing boilers
300 mm
75 mm
200 mm
200 mm
150 mm
300 mm
300 mm
600 mm
1 200 mm
1 200 mm
1 500 mm
300 mm
300 mm
300 mm
300 mm
1 000 mm
600 mm
300 mm
400 mm
Q
S
O
O
Detailed recommendations for flue installation are given in BS 5440:1.
Minimum distance to car
parking space
7
Car
space
20/21
Minimum spacing
2 500 mm
2 500 mm
not recommended
not recommended
4
2.5m