Appendix 1. List Of Parameters For Each Block Of The Eja; A1.1 Resource Block - YOKOGAWA vigilantplant EJA Series User Manual

Eja series differential pressure/pressure transmitter fieldbus communication type
Table of Contents

Advertisement

APPENDIX 1. LIST OF PARAMETERS
FOR EACH BLOCK OF THE EJA
Note:
The Write Mode column contains the modes in which each parameter is write enabled.
O/S:
Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

A1.1 Resource Block

Relative
Index
Parameter Name
Index
0
1000
Block Header
1
1001
ST_REV
2
1002
TAG_DESC
3
1003
STRATEGY
4
1004
ALERT_KEY
5
1005
MODE_BLK
6
1006
BLOCK_ERR
RS_STATE
7
1007
8
1008
TEST_RW
9
1009
DD_RESOURCE
10
1010
MANUFAC_ID
11
1011
DEV_TYPE
12
1012
DEV_REV
13
1013
DD_REV
14
1014
GRANT_DENY
15
1015
HARD_TYPES
16
1016
RESTART
17
1017
FEATURES

APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA

Factory
Write
Default
Mode
Block Tag
TAG:"RS"
= O/S
AUTO
Null
AUTO
1
AUTO
1
AUTO
AUTO
AUTO
Null
Null
0x594543
3
2
2
AUTO
0
Scalar input
Soft write lock
supported
Report supported
A-1
Explanation
Information on this block such as Block Tag, DD Revision,
Execution Time etc.
The revision level of the static data associated with the
resource block. The revision value is incremented each time
a static parameter value in this block is changed.
The user description of the intended application of the block.
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
The actual, target, permitted, and normal modes of the block.
This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
State of the resource block state machine.
Read/write test parameter-used only for conformance testing
and simulation.
String identifying the tag of the resource which contains the
Device Description for this resource.
Manufacturer identification number-used by an interface
device to locate the DD file for the resource.
Manufacturer's model number associated with the resource-
used by interface devices to locate the DD file for the
resource.
Manufacturer revision number associated with the resource-
used by an interface device to locate the DD file for the
resource.
Revision of the DD associated with the resource-used by an
interface device to locate the DD file for the resource.
Options for controlling access of host computer and local
control panels to operating, tuning and alarm parameters of
the block.
The types of hardware available as channel numbers.
bit0: Scalar input
bit1: Scalar output
bit2: Discrete input
bit3: Discrete output
Allows a manual restart to be initiated. Several degrees of
restart are possible. They are 1: Run, 2: Restart resource, 3:
Restart with initial value specified in FF functional spec. (*1),
and 4: Restart processor.
TM
*1: FF-891 Foundation
Specification Function Block
Application Process Part 2.
Used to show supported resource block options.
TA0101-1.EPS
IM 01C22T02-01E

Advertisement