Function Block Execution Control; Block Setting; Link Object - YOKOGAWA vigilantplant EJA Series User Manual

Eja series differential pressure/pressure transmitter fieldbus communication type
Table of Contents

Advertisement

Sub-
Parameter
index
12
FasDllSubsriberTime
WindowSize
13
FasDllSubscriber
SynchronizationDlcep
14
FmsVfdId
15
FmsMaxOutstanding
ServiceCalling
16
FmsMaxOutstanding
ServiceCalled
17
FmsFeatures
Supported
17 VCRs are factory-set as shown in the table below.
Table 5.5 VCR List
Index
VCR
(SM)
Number
293
1
For system management (Fixed)
294
2
Server (LocalAddr = 0xF3)
295
3
Server (LocalAddr = 0xF4)
296
4
Server (LocalAddr = 0xF7)
297
5
Trend Source (LocalAddr = 0x07,
Remote Address=0x111)
298
6
Publisher for AI1 (LocalAddr = 0x20)
299
7
Alert Source (LocalAddr = 0x07,
Remote Address=0x110)
300
8
Server (LocalAddr = 0xF9)
301
9
Publisher for AI2 (LocalAddr = 0x21)
302
10
Not used.
303
11
Not used.
304
12
Not used.
305
13
Not used.
306
14
Not used.
307
15
Not used.
308
16
Not used.
309
17
Not used.

5.5.2 Function Block Execution Control

According to the instructions given in Section 5.3, set
the execution cycle of the function blocks and schedule
of execution.
Description
Not used for EJA.
Not used for EJA.
Sets VFD for EJA to be
used.
0x1: System/network
management VFD
0x1234: Function block
VFD
Set 0 to Server. It is not
used for other applications.
Set 1 to Server. It is not
used for other applications.
Indicates the type of
services in the application
layer. In the EJA, it is
automatically set according
to specific applications.
T0504-2.EPS
Factory Setting
T0505.EPS

5.6 Block Setting

Set the parameter for function block VFD.

5.6.1 Link Object

A link object combines the data voluntarily sent by the
function block with the VCR. The EJA has eleven link
objects. A single link object specifies one combination.
Each link object has the parameters listed in Table 5.6.
Parameters must be changed together for each VCR
because the modifications made to each parameter may
cause inconsistent operation.
Table 5.6 Link Object Parameters
Sub-
Parameters
index
1
LocalIndex
2
VcrNumber
3
RemoteIndex
4
ServiceOperation
5
StaleCountLimit
Set link objects as shown in Table 5.7.
Table 5.7 Factory-Settings of Link Objects (example)
Index
Link Object #
30000
30001
30002
30003
30004
30005
30006
30007
30008
30009
10
30010
11
5-5
5. CONFIGURATION
Description
Sets the index of function
block parameters to be
combined; set "0" for Trend
and Alert.
Sets the index of VCR to
be combined. If set to "0",
this link object is not used.
Not used in EJA. Set to "0".
Set one of the following.
Set only one each for link
object for Alert or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend
Set the maximum number
of consecutive stale input
values which may be
received before the input
status is set to BAD. To
avoid the unnecessary
mode transition caused
when the data is not
correctly received by
subscriber, set this
parameter to "2" or more.
Factory Settings
1
AI1.OUT
VCR#6
2
Trend
VCR#5
3
Alert
VCR#7
4
AI2.OUT
VCR#9
5
Not used
6
Not used
7
Not used
8
Not used
9
Not used
Not used
Not used
IM 01C22T02-01E
T0506.EPS