Honeywell MICRONIK 200 R7426A Installation & Start-Up Instructions page 18

Temperature controller with and without real-time clock
Hide thumbs Also See for MICRONIK 200 R7426A:
Table of Contents

Advertisement

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK
Programming Holiday Schedule (with RTC, only)
The holiday schedule programming is used to program each
day of the year (01.01 ... 31.12.) as a holiday (day type = H1,
H2 or H3) or as a normal day (day type = H0 is default).
+
-
Pushing the
or
button during the first step of the holiday
programming (see Fig. 16) toggles between all programmed
holidays (≠ H0) and displays them (type and date).
If none of the 365 days of a year is programmed to be a
holiday, the actual date is displayed, marked as normal day
(H0).
Pushing the SET button selects the displayed holiday and
enters the adjustment for date and day type.
To program a new holiday, select any holiday, adjust date
(and holiday type if necessary) and confirm the changes by
pushing the SET button. To reset a holiday to normal day, day
type H0 has to be set for the specific day.
Pushing the SEL button returns to the selection mode,
ignoring adjustments which have not been confirmed by the
SET button.
TO
TOGGLE/DISPLAY
OR
PROGRAMMED
HOLIDAY
TO ADJUST
OR
MONTH
TO ADJUST
OR
DAY
TO ADJUST
DAY TYPE (H0,
OR
H1, H2, OR H3)
Fig. 16. Holiday schedule programming
EN1B-0203GE51 R0507C
We
Sa
Th
We
Interpreting Error Messages
Different analog input errors can be identified by the controller
(Error handling). The defective analog input (T1, T2, T3 or
X
) will be displayed in the standard display mode (see Fig.
wrh
17) after the corresponding value is selected.
NOTE: For the external CPA/SPA potentiometer input, no
error message is indicated if the potentiometer or
wiring is defective. In this case, for control point or
setpoint calculation, the following values are used:
for CPATYP 0, 1 or 2 ⇒ CPA value = 0
for CPATYP 3 ⇒ SPA value = control parameter W1
DISPLAY SHOWN IF NO SENSOR
IS CONNECTED DURING POWER-UP
°C
% rh
STANDARD
DISPLAY
AND
: MAIN TEMPERATURE SENSOR T1 IS DEFECTIVE
AND
: LIMITATION OR CASCADE TEMPERATURE SENSOR T2 IS DEFECTIVE
AND
: COMPENSATION TEMPERATURE SENSOR T3 IS DEFECTIVE
SPACE
AND
: ERROR OF HUMIDITY DEVIATION INPUT X
Fig. 17. Error handling
A
SIMULTANEOUSLY
STANDARD
°C
DISPLAY
MODE
°C
PARAMETER
SELECTION
MODE
°C
B
THIS EXAMPLE DESCRIBES THE ADJUSTMENT OF THE
COMPENSATION CHANGEOVER POINT W
(P03).
comp
Fig. 18. Adjustment example
18
DISPLAY SHOWN AFTER ERROR
IDENTIFICATION DURING OPERATION
°C
% rh
Wrh
TEMPERATURE DISPLAY IN
HUMIDITY DEVIATION DISPLAY IN % rh
B
PUSH
FOR APPROX.
2 SEC
PARAMETER
ADJUSTMENT
MODE
°C
PARAMETER
°C
SELECTION
MODE
A
STANDARD
DISPLAY
°C
PUSH UNTIL
NEEDED
VALUE IS
DISPLAYED