Thermal  Expansion
Determine  if  a  check  valve  exists  in  the  inlet  
water  line.  Check  with  your  local  water  utility.  
It  may  have  been  installed  in  the  cold  water  
line  as  a  separate  back  flow  preventer,  or  it  
may  be  part  of  a  pressure  reducing  valve,  water  
meter  or  water  softener.   A  check  valve  located  
in  the  cold  water  inlet  line  can  cause  what  is  
referred  to  as  a  "closed  water  system".   A  cold  
water  inlet  line  with  no  check  valve  or  back  
flow  prevention  device  is  referred  to  as  an  
"open"  water  system.
As  water  is  heated,  it  expands  in  volume  and  
creates  an  increase  in  the  pressure  within  
the  water  system.  This  action  is  referred  to  
as  "thermal  expansion".  In  an  "open"  water  
system,  expanding  water  which  exceeds  the  
capacity  of  the  storage  tank  flows  back  into  
the  city  main  where  the  pressure  is  easily  
dissipated.  
A  "closed  water  system",  however,  prevents  
the  expanding  water  from  flowing  back  into  
the  main  supply  line,  and  the  result  of  "thermal  
expansion"  can  create  a  rapid  and  dangerous  
Inspect  Storage  tank
Inspect  the  storage  tank  for  possible  damage.
pressure  increase  in  the  storage  tank  and  
system  piping.  This  rapid  pressure  increase  can  
quickly  reach  the  safety  setting  of  the  relief  
valve,  causing  it  to  operate  during  each  heating  
cycle.  Thermal  expansion,  and  the  resulting  
rapid  and  repeated  expansion  and  contraction  
of  components  in  the  storage  tank  and  piping  
system  can  cause  premature  failure  of  the  relief  
valve,  and  possibly  the  heater  itself.  Replacing  
the  relief  valve  will  not  correct  the  problem!
The  suggested  method  of  controlling  thermal  
expansion  is  to  install  an  expansion  tank  in  the  
cold  water  line  between  the  storage  tank  and  
the  check  valve  (refer  to  the  illustration  on  the  
page  8).  The  expansion  tank  is  designed  with  
an  air  cushion  built  in  that  compresses  as  the  
system  pressure  increases,  thereby  relieving  
the  over  pressure  condition  and  eliminating  the  
repeated  operation  of  the  relief  valve.  Other  
methods  of  controlling  thermal  expansion  
are  also  available.  Contact  your  installing  
contractor,  water  supplier  or  plumbing  
inspector  for  additional  information  regarding  
this  subject.