d) Pump-Out Frequency Control (S1 dip switch 5 & 6)
The pump-out frequency control is factory set to drain the water tank every 10 cycles,
and generally no adjustment is required. However, if the icemaker needs a pump-out
more often due to local water conditions, the pump-out frequency can be adjusted. The
pump-out frequency control can be set to have a pump-out occur every cycle, or every 2,
5, or 10 cycles. After startup, the first pump-out occurs after the 1st freeze cycle.
e) Harvest Pump Timer (S1 dip switch 7 & 8)
Factory set for proper operation. Do not adjust. Adjustment outside of the
factory default setting may result in damage to the icemaker.
Depending on the harvest pump timer setting, the pump motor energizes and runs for
the last 0, 10, 30, or 50 seconds of harvest. When the pump motor is on, water circulates
over the evaporator. The water valve is energized during harvest for a maximum of
6 minutes or the length of harvest minus 0, 10, 30, or 50 seconds (determined by the
harvest pump timer setting), whichever is shorter.
S1 Dip Switch Setting
No. 5
No. 6
OFF
OFF
ON
OFF
OFF
ON
ON
ON
CAUTION
S1 Dip Switch Setting
No. 7
No. 8
OFF
OFF
ON
OFF
OFF
ON
ON
ON
21
Frequency
Every cycle
Every 2 cycles
Every 5 cycles
Every 10 cycles
Time
(seconds)
0
10
30
50