Finishing

A. Hearth Extension
A hearth extension must be installed with all fi replaces to
protect the combustible fl oor in front of the fi replace from
both radiant heat and sparks. See Figures 8.1 -8.3.
High temperature
(300°F min.) continuous,
non-combustible sealant
HX3 or HX4
Hearth Ext
Tile, stone or other
or equivilent
non-combustible material
insulation
(see Table below)
Floor constructed of wood or
other combustible material
Figure 8.1
Hearth Extension Construction
WARNING
Fire Risk
Metal hearth strips MUST be installed.
Sparks or embers may ignite fl ooring.
This fi replace has been tested and approved for use with a
hearth extension insulated to a minimum R value of 1.16.
To substitute materials for the factory-available hearth ex-
tensions, see Figure 8.3 and calculate insulation alterna-
tives as per Table 8.1 and the following formulas:
Thermal conductivity per inch thickness = k
k = (BTU)(inch) / (foot
Required thickness = Rk
Thermal resistance per inch thickness = r
r = (foot
2
)(hour)(°F) / (BTU)(inch)
Required thickness = R / rB.
Table 8.1
Hearth Extension Insulation Alternatives, R Value = 1.16
Material
Hearth & Home HX3, HX4
USG Micore 300™
USG Durock™ Cement Board
Cement Mortor
Common Brick
Ceramic Tile
Armstrong Privacy Plus
Marble
26
Protective
Metal Hearth
Strip
2 in. (51 mm)
required
2
)(hour)(°F)
k per inch
r per inch
thick
thick
0.43
2.33
0.46
2.18
1.92
0.52
5.0
0.20
5.0
0.20
12.50
0.08
14.3-20.0
0.07-0.05
Heatilator • A36C & A42C • 28396 Rev Y • 10/06
Metal strips are placed 2 in. (51 mm) under the front
of the fireplace and must extend beyond the front
and sides of fireplace opening by 2 in. (51 mm).
Figure 8.2
Positioning the Protective Metal Hearth Strips
Minimum thickness
required
Model #
1/2 in.
1/2 in.
2-1/4 in.
5-7/8 in.
5-7/8 in.
14-5/8 in.
Figure 8.3
16-5/8 in. - 23-3/8 in.
1 in. (25 mm) overlap
WARNING
Fire Risk
Hearth extensions must be installed
exactly as specifi ed.
High temperatures or hot embers may ignite
concealed combustibles.
A
C
Hearth Extension Dimensions
A
in.
52
A36
mm
1321
in.
66
A42
mm
1676
Hearth Extension Dimensions
B
B
C
16
8
406
203
20
8
508
203