Appendix A; Power Vent Locations - Montigo R320-ST Installation & Maintenance Manual

R-series-st residential fireplace
Hide thumbs Also See for R320-ST:
Table of Contents

Advertisement

R320-ST & 420 ST Power Vent Indoor Gas Fireplace
Appendix A: Power Vent Locations
Horizontal
Detail
A = clearance to the termination frame above grade, veranda, porch,
deck, or balcony [30 inches (75 cm) minimum]
B = clearance to door, or sides and top of window, that may be
opened [30 inches (75 cm) minimum for appliances.
C = clearance to bottom of window that may be opened horizontally
[36 inches (92 cm) minimum for appliances.
D = no clearance to permanently closed window when installed with
approved glass penetration termination
E = clearance to permanently closed window [30 inches 75 cm
recommended to prevent condensation on window]
F = vertical clearance to ventilated soffit located above the termination
within a horizontal distance of [30 inches 75 cm] from the centreline
of the termination [30 inches (75 cm) minimum]
G = c l e a r a n c e
t o
u n v e n t i l a t e d
( 7 5
c m )
m i n i m u m
[30 inches (75 cm) minimum to combustibles]
H = clearance to outside corner [30 inches (75 cm) minimum]
I = clearance to inside corner [30 inches (75 cm) minimum]
J = * not to be installed above a meter/regulator assembly within
40" (103 cm) horizontally from the centreline of the regulator
K = clearance to service regulator vent outlet [3 feet minimum in
the United States] [*6 feet (1.8 m) minimum in Canada]
L = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance [16 inches (41 cm) minimum
for appliances ≤100 000 BTU/H (30kW)]
M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]
Page 26
Appendix
s o f f i t
[ 3 0
i n c h e s
t o
n o n - c o m b u s t i b l e s ]
V
Vertical Detail
N =
clearance above paved sidewalk or a paved driveway located
on public property [*7 feet (2.1 m) minimum]
P = clearance under veranda, porch, deck, or balcony [30 inches (75
cm) minimum
to non-combustibles] [30 inches (75 cm) minimum
to combustibles]
Q = clearance above a roof [18 inches (46 cm) minimum]
R = clearance to adjacent walls and neighboring buildings [30 inches
(75 cm) minimum]
S = clearance from corner in recessed location [30 inches (75 cm)
minimum]
T = maximum depth in recessed location [48 inches (122 cm)
minimum]
U = minimum width for back wall of recessed location [60 inches
(150 cm) minimum]
V = minimum horizontal clearance between the frames of two
terminations that are level, (see applicable Detail).
W = horizontal clearance between the frames of two terminations
that are not level. [30 inches (75 cm) minimum]
a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings
only permitted if veranda, porch, deck, or balcony has an open
side that is equal to or greater than the depth of the enclosed area
*
as specified in CGA B149 Installation Codes. Note: local Codes
or Regulations may require different clearance.
XG0772 - 030711