Heat Controller DMH18DB-1 Service Manual page 36

Wall mounted multi-split system air conditioning/heat pump
Table of Contents

Advertisement

Operation
27°C(80.6°F), it operates with Super-Low(while in sleep mode, with the medium airflow speed).
• While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4°F), when above
35°C(95°F) , it operates with the low airflow speed.
• While in defrost control, the indoor is outdoor fans are turned off.
I Defrost Control(Heating)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes
passed from starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C(59°F) even before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes
passed from ending of the first defrost and more than 4 minutes operation of compressor.
I Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C(75.2°F) ≤ Intake Air Temp
21°C(69.8°F) ≤ Intake Air Temp<24°C(75.2°F)
Intake Air Temp<21°C(69.8°F)
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9°F) or more
below the setting temp, the compressor is turned off. When 0.5°C(0.9°F) or more above the setting temp, the
compressor is turned on.
Compressor ON Temp
Compressor OFF Temp
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8°F)≤ Intake Air Temp
24°C(75.2°F)≤ Intake Air Temp<26°C(78.8°F)
22°C(71.6°F)≤ Intake Air Temp<24°C(75.2°F)
18°C(64.4°F)≤ Intake Air Temp<22°C(71.6°F)
Intake Air Temp<18°C(64.4°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature.
36 Multi type Air Conditioner
➲ Fuzzy Operation for Cooling
➲ Fuzzy Operation for Dehumidification
➲ Fuzzy Operation for Heating
➲ Setting Temp +0.5°C(0.9°F)
➲ Setting Temp + 0.5°C(0.9°F)
➲ 25°C(77°F)
➲ Intake Air Temp + 1°C(1.8°F)
➲ Intake Air Temp + 0.5°C(0.9°F)
➲ Intake Air Temp
➲ 18°C(64.4°F)

Advertisement

Table of Contents
loading

Table of Contents