Air Purging; Air Purging With Vacuum Pump - Heat Controller VMH 09 Installation Manual

Version c inverter single zone ductless mini-split heat pump
Hide thumbs Also See for VMH 09:
Table of Contents

Advertisement

VMH Inverter Mini-Split

Air Purging

Air and moisture in the refrigerant system have undesirable effects as indicated below:
• Pressure in the system rises.
• Operating current rises.
• Cooling or heating efficiency drops.
• Moisture in the refrigerant circuit may freeze and block capillary tubing.
• Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated
to remove any noncondensables and moisture from the system.

Air purging with vacuum pump

Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have
been properly connected and all wiring for the test run has been completed. Remove the service
valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the
gas side service valves on the outdoor unit are kept closed at this stage.
Pipe length and refrigerant amount:
Connective Pipe Length Air Purging Method
Less than 16.5 ft. (5m)
More than 16.5 ft. (5m)
INSTALLATION MANUAL
Use vacuum pump
Use vacuum pump
Additional amount of refrigerant to be charged
———————
1/4" (Liquid side)
(Pipe length-16.5ft)x5 oz/ft
13
Heat Controller, Inc.
3/8" (Liquid side)
(Pipe length-16.5ft)x5 oz/ft