Sequenceof Operation For Power Openand Power Closed Valvesor Normally Open Valves; Sequence Of Operation For Heat Pump Systems; Second Stage Heat And Cool Control - Honeywell VisionPRO 8000 Owner's Manual

Visionpro 8000 series touchscreen programmable thermostat
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

VisionPRO
TM 8000
Touchscreen
Programmable
Thermostat
Table
10. Sequence
of Operation
for Power
Open
and Power
Closed
Valves
or Normally
Open
Valves.
System
Setting
Fan Setting
Call for Action
Energize
Terminals
Screen
message
Off
N/A
None
Y
None
Heat
N/A
None
Y
None
Heat
N/A
Heat
W
Heat On
Table
11. Sequence
of Operation
for Heat Pump
Systems.
System
Setting
Fan Setting
Call for Action
Energize
Terminals
Screen
message
Off
Auto
None
OiB a
None
Cool
Auto
None
O/B a
None
Cool or Auto
Auto
Stage
1 Cooling
Y, G, O/B a
Cool On
Cool or Auto
Auto
Stage
1 and Stage
2 Cooling
Y, Y2 d, G, O/B a
Cool On
Heat
Auto
None
O/B a
None
Heat or Auto
Auto
Stage
1 Heating
Y, G, O/B a
Heat On
Heat or Auto
Auto
Stage
1 and Stage
2 Heating
Y, AUX c, G, O/B a
Aux Heat On
Heat or Auto
Auto
Stage
1, 2 and 3 Heating
Y, Y2 d, AUX e, G, OiB a
Aux Heat On
Em. Heat
Auto
None
L b, O/B a
None
Em. Heat
Auto
Stage
1 Heating
E, G, L b, O/B a
Heat On
Em. Heat
Auto
Stage
1 and Stage
2 Heating
E, AUX, G, Lb, O/B a
Aux. Heat On
aConfigure
O/B in installer
Setup.
Based
on last piece of equipment
called
(cooling
= O or heating
= B).
bRed LED is on. See LED
Indication
section
for more details.
clf Installer
Setup
System
Type is set to 2Heat/1Cool
Heat Pump with Auxiliary
Heat.
dlf Installer
Setup
System
Type
is set to 3Heat!2Cool
Heat Pump
with Auxiliary
Heat.
eThis terminal
does not energize
if Installer
Setup
System
type is set to 2 Heat/2
Cool
Heat Pump with
no Auxiliary
Heat.
Second Stage Heat and Cool Control
While
maintaining
setpoint,
several
factors
affect
when 2nd
stage energizes
such as load conditions,
environmental
conditions,
P+I control,
and home
insulation.
The second
stage energizes
when the thermostat
senses
1st stage is
running
at 90% capacity.
This operation
is droopless
control.
35
68-0280