Table 1. Installer Setup
Setup functions
Setting & Options (factory
default in bold)
0520
U/V lamp change
0
Off
reminder
1
365 calendar days
0530
Adaptive Intel-
1
On
ligent Recovery
0
Off
TM
0540
Program periods
4
4 periods (Wake,
Leave, Return, Sleep)
2
2 periods (Wake, Sleep)
0580
Compressor
5
5-minute compressor
protection
off time
[Other options: 0–4
minutes]
0600
Heat temperature
90
Max. heat temperature
range stop
setting is 90°F (32°C)
[Other options: 40-89°F
(4°C to 32°C)]
0610
Cool temperature
50
Min. cool temperature
range stop
setting is 50°F (10°C)
[Other options: 51-99°F
(11°C to 37°C)]
0640
Clock format
12
12-hour time
24
24-hour time
0650
Extended fan
0
Off
timer (heat)
90
Fan runs for 90 seconds
after call for heat ends
0660
Extended fan
0
Off
timer (cool)
90
Fan runs for 90 seconds
after call for cooling ends
0670
Keypad Lockout
0
Unlocked
1
Partially locked
2
Fully locked
6
Table 1. Installer Setup
Setup functions
Setting & Options (factory
default in bold)
0680
Heat temperature
2
Standard temperature
control
control (recommended)
1
Select if inside tempera-
ture is consistently over
setting
3
Select if inside tempera-
ture is consistently under
setting
0690
Cool temperature
2
Standard temperature
control
control (recommended)
1
Select if inside tempera-
ture is consistently over
setting
3
Select if inside tempera-
ture is consistently under
setting
0700
Temperature
0
No offset
display offset
[Other options: -3, -2,
-1, 1, 2, 3°F (-1.5°C to
1.5°C)]
0710
RESET
0
No reset
1
Reset installer options
& program schedule to
factory default
7
InsTalleR sysTem TesT
The Installer Test is part of the Installer Setup Menu.
1.
Enter the Installer System Test by entering the Installer
Setup and pressing t repeatedly until "Test" appears.
DONE
M24083
2.
Use arrow to change test and system status as
required.
TEST NUMBER
SYSTEM STATUS
DONE
M24085
3.
Press DONE to exit.
8
sysTem TesTs
Test the system's heating, cooling, fan and emergency heat.
Available tests vary by thermostat and system type.
Table 2. Installer System Test
System Test
Test Type
System Status Number
Number
and Description
Test 1
Cooling System
0
Off
Test
1
Compressor and
fan on
2
Second stage
compressor on
Test 2
Fan System
0
Off
Test
1
Fan on
Test 3
Heating System
0
Off
Test
1
Heat on
2
Second stage heat
(Aux. heat) on
3
Third stage heat
(Auxiliary heat) on
Test 4
Emergency
0
Off
Heat Test
1
Em. Heat and fan on
2
Auxiliary heat on
Press the DONE button to exit the Installer System Test.
caution
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing. To
prevent equipment damage, avoid cycling the compres-
sor quickly.
9
VisionPRO
8000
®
Thermostats
InsTalleR seTuP and
sysTem TesT POckeT GuIde
InsTalleR seTuP
1.
Press SYSTEM.
FAN
Inside
ON
AUTO
SYSTEM
HEAT
AM
SCHED
HOLD
M24079
69-1871-1

Advertisement

loading

Summary of Contents for Honeywell VisionPRO 8000

  • Page 1 InsTalleR sysTem TesT sysTem TesTs Table 1. Installer Setup Table 1. Installer Setup Setup functions Setting & Options (factory Setup functions Setting & Options (factory default in bold) default in bold) The Installer Test is part of the Installer Setup Menu. Test the system’s heating, cooling, fan and emergency heat.
  • Page 2 Toronto, Ontario M1V 4Z9 0510 Humidifier pad change reminder 90 calendar days http://yourhome.honeywell.com 180 calendar days 365 calendar days ® U.S. Registered Trademark © 2006 Honeywell International Inc. US Patent No. 6595430, D509151; other Patents Pending. All Rights Reserved 69-1871-1 M.S. Rev. 09-06...