HEATER. USE OF THIS FURNACE DURING CONSTRUCTION AND FINISHING PHASES OF A STRUCTURE IS CONSIDERED AS "OPERATION IN A CORROSIVE ATMOSPHERE" AND "UNUSUAL, NEGLIGENT OR IMPROPER USE" AND AS SUCH ARE CONSIDERED EXCLUSIONS BY THE BARD MANUFACTURING COMPANY LIMITED WARRANTY. Bard Manufacturing Company...
GETTING OTHER INFORMATION and PUBLICATIONS FOR MORE INFORMATION, CONTACT These publications can help you install the furnace. You THESE PUBLISHERS: can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave.
INSTALLATION and OPERATING INSTRUCTIONS LOCATING THE FURNACE EQUIPMENT SELECTION When installing the furnace be sure to provide adequate An accurate heating load calculation must be conducted space for easy service and maintenance. Locate the using American Society of Heating, Refrigeration and furnace as close to the chimney as practical, giving Air Conditioning Engineers (ASHRAE) or Air consideration to the accessibility of the oil burner,...
AIR DUCT SYSTEMS For top discharge FH and FL models, when coils are installed without using Bard coil cabinets or coils of Short cycling because of limit control operation can be another brand are used, the coil drain pan should be...
WIRING FIELD WIRING All wiring must conform to the National Electrical FACTORY WIRING Code and all local codes. A separate fuse or breaker All units are fully factory wired. Multispeed blowers should be used for the furnace. are factory wired on high speed for cooling/manual fan operation.
FIGURE 4 TYPICAL UNIT SETUP FLF UNIT SHOWN WARNING TYPICAL UNIT ALL WIRING MUST CONFORM TO THE SETUP NATIONAL ELECTRIC CODE AND ALL LOCAL (FLF UNIT SHOWN) CODES. Left side high voltage (unit power) entrance Inspection door Left side low voltage (thermostat) Right side entrance...
FIGURE 5 TYPICAL FLUE INSTALLATION REQUIREMENTS FRONT FLUE LOWBOY MODEL SHOWN (REPRESENTS ALL MODELS) INSTALLER NOTE: Thimble Follow all appropriate standards for installing needed venting system. Draft Regulator (Be sure to follow installation inst. supplied with 1/4 inch per regulator). 1 foot rise 90°...
OIL LINE PIPING BECKETT AFG OIL BURNER First determine whether the pipe system is to be a single This furnace is equipped with a high static Beckett AFG line system or a two line system. All connections must oil burner which is designed to produce adequate draft in be absolutely air tight or you will have a malfunction of nearly any vertically vented application.
BECKETT SOLID STATE IGNITER These controls were selected for their proven high quality, dependability, and serviceability. With proper This igniter differs from the traditional iron core maintenance this burner assembly will provide many transformer in that it produces a 14,000 volt spark years of reliable service.
BECKETT R7184B PRIMARY OPERATIONAL GUIDE Pre-Purge Delay – 15 seconds on delay LED Codes – Flashing 1/2 second on / 1/2 second off – system is locked out or in restricted mode (hard lockout). – Flashing 2 seconds on / 2 seconds off – control is in recycle mode (soft lockout). –...
TABLE 4 FURNACE DATA 70 degree hollow cone spray pattern, 100 PSIG pump pressure Annual fuel utilization efficiency and heating capacity based upon U.S. Government standard test using D.O.E. isolated combustion rating procedure. BURNER SETUP AND ADJUSTMENT 1. PREPARATION STEPS PROCEDURES A.
Page 17
K. Adjust Air Setting Examine the smoke - CO It should be located as close as possible to the plot and, keeping in mind the curve of oil burner. Care should be taken to prevent air Figure 6, note the location of the “knee” where leakage in the oil suction line.
4. FINAL CHECKS SHORT FORM ADJUSTMENT PROCEDURE M. Measure Stack Temperature Operating the unit at an excessive firing rate will generate Some burner service organizations may wish to more heat than the heat exchanger can utilize perform a shorter procedure for the adjustment of oil and result in unnecessary heat loss up the burners.
FIGURE 8 TYPICAL SMOKE – CO CHART WITH ADJUSTMENT RANGE High Air Settings CO Curve from plotted points Plotted point Normal adjustment range Tolerance to "knee" "Best" air setting Plotted point Plotted point "Knee" Percent CO in Flue Gas Technician's plotting area MIS-1827 Percent CO in Flue Gas...
SPACING OF ELECTRODES COMBUSTION AIR REQUIREMENTS The electrodes should be spaced 5/32” apart. They This furnace must be installed in a location where a should extend 1/16” beyond the end and 5/16” above sufficient supply of combustion air is available for the the center of the nozzle tip as shown in Figure 10.
FIGURE 11 COMBINATION AIR BOOT ASSEMBLY COMBUSTION AIR BOOT ASSEMBLY USE THIS KNOCKOUT INTAKE FOR OIL LINE TUBE BURNER ASSEMBLY REMOVE PUMP TO ASSEMBLE INNER AIR BOOT REMOVE KNOCKOUT IN LEFT SIDE INSERT OUTER AIR BOOT AND SECURE FLANGE TO UNIT MIS-1833 MAKE ALL SETTINGS ACCORDING TO MANUAL...
APPLIANCES LOCATED IN CONFINED TABLE 8 SPACES SQUARE FEET REQUIRED TO In unconfined spaces in buildings, infiltration may be QUALIFY AS UNCONFINED SPACE adequate to provide air for combustion, ventilation, and dilution of flue gases. However, in buildings of unusually tight construction, additional air shall be provided using the method described under “All Air From Outdoors”...
ALL VENTILATION AIR FROM OUTDOORS TABLE 9 MINIMUM VENTILATION OPENINGS A. The confined space shall be provided with two permanent openings, one in or near the top of the enclosure and one in or near the bottom. The l i t openings shall communicate directly, or by means of ducts with outdoors or to such spaces (crawl or attic) that freely communicate with outdoors.
FIGURE 14 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC NOTE: The inlet and outlet air openings shall each have a free area of not less than one square inch per 4,000 BTU per hour (35 square inches per gallon per hour) of the total input rating of all appliances in the enclosure.
A barometric damper is supplied with the furnace and LOUVERS AND GRILLES must be installed in the flue pipe observing the In calculating free area for ventilation and combustion instructions packaged with the damper control. The air requirements, consideration shall be given to the barometric damper opening must be located in the same blocking effect of louvers, grilles, or screens protecting atmospheric pressure zone as the combustion air inlet to...
AIR FILTERS Only Lo-Boy models are shipped with air filters. Filter TABLE 11 kits are available from your local distributor for Upflow FILTER SIZES FOR OIL FURNACES and Counterflow models. Knockouts are provided in the sides of the FH series models to facilitate the cutting of the return openings.
LO-BOY MODELS – FILTER LOCATIONS Lo-boy models have the filter installed in the return air cabinet section of the furnace. It is accessible from the rear of the furnace by removing the blower/filter access door. The electrical switch should be turned “off” prior to removing the access door.
MAINTENANCE LUBRICATION B. Ignition Failure – Test by closing oil supply while burner is off. Run through starting No lubrication is required for either the burner or the procedure. The primary control will attempt blower motor. Both are permanently lubricated. three trials for ignition.
COMBINATION COMBUSTION WARNING CHAMBER/BURNER MOUNTING SYSTEM The furnace has been designed with a combustion The procedures described in Figures 19 and chamber mounting system that enables service 20 should be conducted only by a qualified personnel to remove the combustion chamber, its service technician.
TO REMOVE THE ENTIRE COMBUSTION TO REMOVE BURNER ONLY CHAMBER MOUNTING SYSTEM Disconnect fuel line, power cord and wires from T, T Disconnect fuel line, power cord and wires from T, T on primary control. Loosen (3) 1/4 inch bolts securing on primary control.
COMMON CAUSES OF TROUBLE PUMP SQUEALS OR CHATTERS This may be caused by air in pipes. Check all joints in CAUTION the oil supply pipe for leaks. Check strainer in pump; if dirty, clean. To avoid accidents, always open main switch INSUFFICIENT HEAT (OFF position) when servicing the burner.
BLOWER SYSTEM RESISTANCE CHARTS CHART 1 CHART 4 FH085D36E DATA FLF/FLR085D36E DATA CHART 5 CHART 2 FLF/FLR110D48E DATA FH110D48E DATA CHART 3 CHART 6 FH110D60E DATA FLF/FLR110D60E DATA Manual 2100-422 Page...
FH SERIES WIRING DIAGRAM UNIT NOTES PURPLE PRIMARY IF PRIMARY LIMIT WIRES ARE TO BE REPLACED, PURPLE LIMIT BACKUP USE WIRE WITH INSUL. CONTROL LIMIT TEMP. RATING OF 200°C. BURNER ASS'Y HEATING SPEED CONNECTION POINT. COOLING SPEED CONNECTION POINT. VALVE OIL VALVE ONLY ONE HEATING AND COOLING SPEED...