Routinemaintenance - Friedrich PTAC Series Installation & Operation Manual

Packaged terminal air conditioners & heat pumps
Hide thumbs Also See for PTAC Series:
Table of Contents

Advertisement

920-087-04
(8-05)
J. RoutineMaintenance
NOTE: Units are to be inspected and serviced by qualified service personnel only.
1. Clean the unit air intake filter at least every 300 to 350 hours
of operation. Clean the filters with a mild detergent in warm
water and allow to dry thoroughly before reinstalling.
2. The indoor coil (evaporator coil), the outdoor coil (condenser
coil) and base pan should be inspected periodically (yearly
or bi-yearly) and cleaned of all debris (lint, dirt, leaves,paper,
etc.). Clean the coils and base pan with a soft brush and
compressed air or vacuum. If using a pressure washer, be
careful notto bend the aluminium fin pack. Use a sweeping
up and down motion in the direction of the vertical aluminum
fin pack when pressure cleaning coils. Cover all electrical
components to protect them from water or spray.
Before reinstalling the chassis in the sleeve, inspect the
indoor blower housing, blower wheel, condenser fan blade,
and condenser shroud periodically (yearly or bi-yearly) and
clean of all debris (lint, dirt, mold, fungus, etc.) Clean the
blower housing area and blowerwheel with an antibacterial
/ antifungal cleaner. Use a biodegradable cleaning agent
and degreaser on condenser fan and condenser shroud.
Use warm or cold water when rinsing these items. Allow
the unit to dry thoroughly, inspect all gasket material for
deterioration (replace as necessary), and then reinstall the
chassis in the sleeve.
,
,
Periodically (at least yearly or bi-yearly): inspect all control
components, both electrical and mechanical, as well as the
power supply. Use proper testing instruments (voltmeter,
ohmmeter, ammeter, wattmeter, etc.) to perform electrical
tests. Use an air conditioning or refrigeration thermometer
to check room, outdoor and coil operating temperatures.
Use a sling psychrometer to measure wet bulb temperatures
indoors and outdoors.
Inspect the surrounding area (inside and outside) to ensure
that the units' clearances have not been compromised or
altered.
Inspect the sleeve and drain system periodically (at least
yearly or bi-yearly) and clean of all obstructions and debris.
Clean both areas with an antibacterial and antifungal
cleaner. Rinse both items thoroughly with water and ensure
that the drain outlets are operating correctly. Check the
sealant around the sleeve and reseal areas as needed.
Clean the front cover when needed. Use a mild detergent.
Wash and rinse with warm water. Allow them to dry
thoroughly before reinstalling them in the chassis.
NOTE: Do not use a caustic coil cleaning agent on coils
or base pan. Use a biodegradable cleaning agent and
degreaser.
Figure16
Components
Filters
Condenser Fan Blade
Indoor Blower
Discharge Air Grille
Indoor Blower
Housing
Condenser Gasket
Condenser Shroud
Outdoor
Grille
3ressor
Wall Sleeve
Return Air
Control Panel
Grille
Evaporator
Coil
22