Electrical Preparation
No. of Disk Systems
on Circuit
1
2
3
4
Incoming Voltage
AC RMS
100 – 120 volts
200 – 240 volts
Caution
Multiple disk systems are not recommended on 110 V circuits. The
combined current drawn by multiple systems quickly exceeds 110-V
capacity.
36
Inrush Currents and Duration
Up to 20 amps for 10 to 12 milliseconds
Up to 40 amps for 10 to 12 milliseconds
Up to 60 amps for 10 to 12 milliseconds
Up to 80 amps for 10 to 12 milliseconds
Maximum RMS Current Drawn by One
Disk System
5.3 – 6.5 amps
2.6 – 3.2 amps